The product uses clean dry air as the insulating medium, filled in a sealed gas compartment welded from 304 stainless steel. It is environmentally friendly, in line with national development needs, and represents the forefront of the development of box-type GIS.
QCXE-12 environmental-friendly GIS gas-insulated metal-enclosed switchgear
|
Project Unit |
Unit |
Parameters |
||
|
Rated voltage |
kV |
12 |
||
|
Rated current |
kA |
630, 1250, 2500, 3150 |
||
|
Rated frequency |
Hz |
50 |
||
|
Rated power frequency withstand voltage (1min) |
Phase to phase, phase to ground |
kV |
42 |
|
|
Fracture |
kV |
48 |
||
|
Rated lightning impulse (1.2/50μs) |
Phase to phase, phase to ground |
kV |
75 |
|
|
Fracture |
kV |
85 |
||
|
Main circuit temperature rise |
A |
1.1*Ir |
||
|
Rated short-time breaking current |
kA |
25, 31.5, 40 |
||
|
Rated short-circuit closing current |
kA |
63, 80, 100 |
||
|
Rated short-time withstand current |
kA |
25, 31.5, 40 |
||
|
Rated peak withstand current |
kA |
63, 80, 100 |
||
|
Insulating gas |
/ |
Dry air |
||
|
Compartment pressure |
Minimum functional pressure |
MPa |
0 |
|
|
Air tank protection level |
/ |
IP67 |
||
|
Protection class of shell |
--/ |
IP4X |
||
|
Rated operating voltage |
V |
DC220 |
||
|
Rated auxiliary voltage |
V |
AC220 |
||
|
Overall dimension (W×D×H) |
mm |
600 × 1250 × 2250(630, 1250A) |
||
|
800 × 1600 × 2250(2500A) |
||||
|