Rated capacity (kVA) |
Voltage combination and tap range |
Bonding Group Label |
Level 1 Energy Efficiency |
Level 2 Energy Efficiency |
Level 3 Energy Efficiency |
Short circuit impedance (%) |
|||||
|
High voltage (kV) |
High voltage tap range (%) |
Low voltage (kV) |
No-load loss (kW) |
Load loss (kW) |
No-load loss (kW) |
Load loss (kW) |
No-load loss (kW) |
Load loss (kW) |
|||
|
50 |
33 35 36.75 37 38.5 |
± 5% or ± 2 × 2.5% |
0.4 0.433 0.48 0.57 0.69 |
Dyn11/Yyn0 |
0.102 |
1.14/1.08 |
0.115 |
1.20/1.14 |
0.128 |
1.20/1.14 |
6 or 6.5 |
|
100 |
0.147 |
1.91/1.81 |
0.166 |
2.01/1.91 |
0.184 |
2.01/1.91 |
|||||
|
160 |
0.179 |
2.68/2.55 |
0.202 |
2.82/2.68 |
0.224 |
2.82/2.68 |
|||||
|
200 |
0.218 |
3.15/3.00 |
0.245 |
3.32/3.16 |
0.272 |
3.32/3.16 |
|||||
|
315 |
0.307 |
4.51/4.30 |
0.346 |
4.75/4.53 |
0.384 |
4.75/4.53 |
|||||
|
400 |
0.371 |
5.45/5.20 |
0.418 |
5.74/5.47 |
0.464 |
5.74/5.47 |
|||||
|
500 |
0.435 |
6.56/6.25 |
0.49 |
6.91/6.58 |
0.544 |
6.91/6.58 |
|||||
|
630 |
Dyn11/Yyn0 |
0.531 |
7.47 |
0.598 |
7.86 |
0.664 |
7.86 |
||||
|
800 |
0.627 |
8.93 |
0.706 |
9.4 |
0.784 |
9.4 |
|||||
|
400 |
± 4 × 2.5% ± 2 × 2.5% |
0.371 |
4.90 |
0.418 |
5.16 |
0.464 |
5.16 |
||||
|
630 |
0.525 |
7.05 |
0.591 |
7.42 |
0.656 |
7.42 |
|||||
|
800 |
0.627 |
8.44 |
0.706 |
8.88 |
0.784 |
8.88 |
|||||
|
1250 |
0.896 |
13.2 |
1.008 |
13.9 |
1.12 |
13.9 |
|||||
|
1600 |
1.082 |
15.8 |
1.217 |
16.6 |
1.352 |
16.6 |
|||||
|
Note: 1. For the transformer with rated capacity ≤ 500kVA, the load loss value above the slash in the table is applicable to Dyn11, and the load loss value below the slash is applicable to Yyn0; 2. According to user requirements to manufacture a variety of special parameters and performance of the transformer. 3. The loss parameters are converted according to the purchase standard and loss level of Q/GDW-1300 series -2018 station transformer. |
|||||||||||