500kV Class 120MVA ~ 1170MVA Three-phase Double-winding Off-circuit Tap Changer Power Transformer
Negotiable
China
Southern Zone, High-tech Development Zone, Tai'an City, shandong Province
0538-8933861
Online Contact
Favorite
Product Introduction

Rated capacity (MVA)

Voltage combination

Bonding Group Label

Level 1 Energy Efficiency

Level 2 Energy Efficiency

Level 3 Energy Efficiency

Short circuit impedance (%)

High voltage (kV)

Low voltage (kV)

No-load loss (kW)

Load loss (kW)

No-load loss (kW)

Load loss (kW)

No-load loss (kW)

Load loss (kW)

120

500

525

550

13.8;15.75

YNd11

41

356

49

356

60

375

14

160

50

441

59

441

72

466

240

69

599

81

599

100

632

300

13.8;15.75;18

80

707

94

707

116

746

370

15.75;18;20

94

810

111

810

136

855

400

18;20;24

96

855

114

855

140

903

420

15.75;18;20

102

860

120

860

148

907

14 or 16

480

15.75;18;20

110

954

130

954

160

1007

600

15.75;18;20;24

143

1202

169

1202

208

1268

720

18;20;24

168

1382

198

1382

244

1458

750

20;22

173

1422

205

1422

252

1501

16 or 18

780

22

176

1467

208

1467

256

1549

860

190

1575

224

1575

276

1663

1140

27

237

1949

280

1949

344

2057

1170

242

1980

286

1980

352

2090