Rated capacity (kVA) |
Voltage combination and tap range |
Bonding Group Label |
Level 1 Energy Efficiency |
Level 2 Energy Efficiency |
Level 3 Energy Efficiency |
No-load current (%) |
Short circuit impedance (%) |
|||||
|
High voltage (kV) |
High voltage tap range (%) |
Low voltage (kV) |
No-load loss (kW) |
Load loss (kW) |
No-load loss (kW) |
Load loss (kW) |
No-load loss (kW) |
Load loss (kW) |
||||
|
400 |
66 or 69 |
± 2 × 2.5% |
0.4 |
Dyn11 |
0.51 |
5.7 |
0.58 |
5.7 |
0.64 |
6 |
0.3/0.5 |
8 |
|
630 |
0.66 |
6.77 |
0.74 |
6.77 |
0.82 |
7.13 |
0.3/0.5 |
|||||
|
800 |
0.77 |
7.98 |
0.86 |
7.98 |
0.96 |
8.4 |
0.3/0.5 |
|||||
|
1000 |
0.87 |
9.31 |
0.98 |
9.31 |
1.09 |
9.8 |
0.3/0.5 |
|||||
|
630 |
± 4 × 2.5% |
0.66 |
6.77 |
0.74 |
6.77 |
0.82 |
7.13 |
0.3/0.5 |
||||
|
800 |
0.77 |
7.98 |
0.86 |
7.98 |
0.96 |
8.4 |
0.3/0.5 |
|||||
|
1000 |
0.87 |
9.31 |
0.98 |
9.31 |
1.09 |
9.8 |
0.3/0.5 |
|||||
|
1250 |
1.02 |
11.4 |
1.15 |
11.4 |
1.28 |
12 |
0.3/0.5 |
|||||
|
1600 |
1.27 |
13.3 |
1.43 |
13.3 |
1.59 |
14 |
0.3/0.5 |
|||||
|
2500 |
1.54 |
18.05 |
1.73 |
18.05 |
1.92 |
19 |
0.3/0.5 |
|||||
|
Note: 1. According to the special technical specification of national grid procurement standard, the no-load current value above the slash in the table is the required value of rated no-load current, and the value below the slash is 1.1 times the required value of load current during overvoltage; 2. According to user requirements to manufacture a variety of special parameters and performance of the transformer. |
||||||||||||