The BTK-110kV/220kV transformer neutral point accessory combination mainly includes the following related equipment: neutral point disconnect switch, discharge gap, zinc oxide lightning arrester, and current transformer for measuring discharge current. To ensure an aesthetically pleasing and convenient equipment arrangement, a separate T-shaped or portal-shaped bracket can be designed based on the user's equipment selection, integrating the neutral point disconnect switch, discharge gap, lightning arrester, and other neutral point accessory equipment into a single unit that facilitates on-site construction and installation. This transformer neutral point accessory combination equipment provides protection against lightning overvoltage, switching overvoltage, and temporary overvoltage at the transformer neutral point.
Neutral Point Complete Protection Device BTK-110/220
|
Product Model |
BTK-110 |
BTK-220 |
|
|
Rated voltage of transformer |
126 |
252 |
|
|
Transformer neutral point withstand voltage |
8/20μs lightning impulse withstand voltage KV (peak value) |
250 |
400 |
|
1min power frequency withstand voltage KV (effective value) |
95 |
200 |
|
|
Isolating switch |
Model |
GW13-72.5GW8-72.5 |
GW13-126GW8-126 |
|
Rated current A |
630 |
||
|
Main loop resistance μΩ |
400 |
450 |
|
|
Insulation distance of fracture after opening of isolating switch mm |
≥ 650 |
≥ 1000 |
|
|
Operating mechanism |
CS17A hand force mechanism or CJTKB electric mechanism |
||
|
Zinc Oxide Arrester |
Model |
YH1.5W-72/186 |
YH1.5W-144/320 |
|
Rated voltage KV (effective value) |
72 |
144 |
|
|
Continuous operating voltage KV (effective value) |
58 |
116 |
|
|
8/20μs lightning impulse current residual voltage is not more than KV |
186 |
320 |
|
|
DC 1mA reference voltage not less than KV |
105 |
205 |
|
|
2ms square wave flow capacity A |
400 |
||
|
Discharge Gap |
Type |
Rod gap, spherical electrode |
|
|
Power frequency dry discharge voltage ± 10% KV |
83 |
164 |
|
|
Distance range of gap electrode mm |
90~135 |
250~320 |
|
|
Current transformer |
Model |
LMZW-10 |
|
|
Transformation ratio |
100/5, 200/5, 300/5, 400/5, 500/5, 600/5 |
||
|
Secondary protection level |
5P/10, 10P/10, 10P/20 |
||
|
Capacity |
10VA, 20VA, 30VA |
||
|
Weight |
Not greater than kg |
300 |
400 |