No. |
Technical parameters |
Technical Requirement Value |
|||||||||||
|
1 |
Nominal system voltage kv (effective value) |
66 |
110 |
220 |
500 |
||||||||
|
2 |
Rated voltage of arrester Ur kV (effective value) |
84 |
90 |
96 |
100 |
102 |
108 |
200 |
204 |
216 |
420 |
444 |
468 |
|
3 |
Arrester continuous operating voltage Uc kv (effective value) |
67.2 |
72.5 |
75 |
78 |
79.6 |
84 |
156 |
159 |
169 |
318 |
324 |
330 |
|
DC 1mA reference voltage UImA kV |
121 |
130 |
140 |
145 |
148 |
157 |
290 |
296 |
314 |
565 |
597 |
630 |
|
|
5 |
Leakage current at 0.75 times Us-μA |
20 |
20 |
30 |
40 |
||||||||
|
6 |
Power frequency reference voltage 2 kV (peak/√2) |
84 |
90 |
96 |
100 |
102 |
108 |
200 |
204 |
216 |
420 |
444 468 |
|
|
Power frequency reference current (resistive) mA |
1 |
1 |
5 |
||||||||||
|
7 |
Nominal discharge current kA (peak) |
10 |
10 |
10 |
20 |
||||||||
|
8 |
Steep wave impulse current kv (peak value) at 10kA |
254 |
270 |
288 |
291 |
297 |
315 |
582 |
594 |
630 |
1170 * |
1238 * |
1306 * |
|
Residual voltage (s) Lightning surge current below 10kA kV (peak value) |
221 |
235 |
250 |
260 |
266 |
281 |
520 |
532 |
562 |
1046 * |
1106 * |
1166 * |
|
|
Operating impulse current below 0.5kA kV (peak value) |
188 |
201 |
213 |
221 |
226 |
239 |
442 |
452 |
478 |
858 |
907 |
956 |
|
|
9 |
Resistive current-1A |
250 |
250 |
250 |
600 |
||||||||
|
Continuous current Full current: - μA |
800 |
900 |
900 |
2000 |
|||||||||
|
10 |
Large current impact withstand 4/10 2 times kA (peak) |
100 |
100 |
100 |
100 |
||||||||
|
11 |
Local discharge under 1.1 times Uc ≤ pC |
5 |
5 |
5 |
5 |
||||||||
|
12 |
Insulation lightning impulse withstand voltage ≥ kV (peak) |
350 |
550 |
1050 |
1675 |
||||||||
|
Operating impulse withstand voltage≥ kv (peak) |
- |
- |
- |
1300 |
|||||||||
|
Power frequency dry (wet) withstand voltage ≥ kV (effective value) |
160 |
230 |
460 |
740 |
|||||||||
|
Serial Number |
Technical parameters |
Technical Requirement Value |
|||||||||
|
1 |
Nominal system voltage kv (effective value) |
10 |
35 |
110 neutral point |
220 neutral point |
330 |
|||||
|
2 |
Rated voltage of arrester Ur: kV (effective value) |
17 |
17 |
51 |
54 |
60 |
72 |
144 |
300 |
312 |
|
|
Surge arrester continuous operating voltage Uc. kv (effective value) |
13.6 |
13.6 |
40.8 |
43.2 |
48 |
58 |
116 |
228 |
237 |
||
|
4 |
DC 1mA reference voltage U 1mA kV |
24 |
25 |
73 |
77 |
85 |
103 |
205 |
425 |
442 |
|
|
Leakage current s μA at 0.75 times Us |
20 |
30 |
|||||||||
|
6 |
Power frequency reference voltage 2 kV (peak/✓ 2) |
17 |
17 |
51 |
54 |
60 |
72 |
144 |
300 |
312 |
|
|
Power frequency reference current (resistive) mA |
1 |
2 |
|||||||||
|
7 |
Nominal discharge current kA (peak) |
5 |
5 |
1.5 |
1.5 |
10 |
|||||
|
Residual pressure ≤ |
Steep wave impulse current kv (peak value) at 10kA |
51.8 |
57.5 |
154 |
- |
- |
- |
814 |
847 |
||
|
Lightning impulse current under 10kA kV (peak) |
45 |
50 |
134 |
144 |
186 |
320 |
727 |
760 |
|||
|
Operating impulse current kv at 0.5kA (peak value) |
38.3 |
42.5 |
114 |
135 |
174 |
299 |
618 |
643 |
|||
|
9 |
Continuous current |
resistive current s 1A |
100 |
250 |
250 |
300 |
|||||
|
Full current: s μA |
500 |
800 |
900 |
1000 |
|||||||
|
10 |
Large current impact withstand 4/10 2 times kA (peak) |
65 |
65 |
100 |
100 |
||||||
|
11 |
Local discharge under 1.1 times Uc ≤ pC |
5 |
5 |
5 |
5 |
||||||
|
12 |
Tolerance |
Lightning impulse withstand voltage 2kV (peak) |
95 |
200 |
325 |
550 |
1306 |
||||
|
Insulation voltage |
Operating impulse withstand voltage akv (peak) |
- |
- |
- |
- |
1056 |
|||||
|
1min power frequency dry (wet) withstand voltage ≥ kv (effective value) |
42 |
95 |
140 |
230 |
567 |
||||||