12kV (SF6) Gas-insulated Switchgear
Negotiable
China
No.12 Hongtai Road, Huaming Street, Dongli District, Tianjin City
15822469629
Online Contact
Favorite
Product Introduction

The GTP5.1-12 series gas-insulated switchgear is used in 12kV systems with gas-insulated metal-enclosed switchgear, featuring vacuum arc extinction, SF6 insulation, a slight positive pressure of 0.02MPa, and a gas tank protection rating of IP67. It is unaffected by external environmental conditions, offering simple operation, full enclosure, maintenance-free design, and long lifespan, making it particularly suitable for special environments such as high altitudes, humid areas, sandy and dusty regions, and salt spray conditions.

Product Features

SF6 insulation, vacuum arc extinction.

Superior insulation performance, with overall partial discharge <10pC.

Optimized electric field simulation, meeting insulation performance requirements at zero gauge pressure.

Special heat dissipation structure, achieving 1×4000A natural heat dissipation.

Compact and reliable structure, saving space, with a 60% reduction in volume compared to traditional switchgear.

Advanced process control, laser welding, and helium leak detection ensure gas sealing performance, with an annual gas leakage rate <0.05%.

The high-voltage circuit is sealed inside the gas tank, unaffected by the environment, making it especially suitable for harsh conditions such as humidity, salt spray, and sandy or dusty areas, and can be used at altitudes up to 5000m.

High performance, with a mechanical lifespan of 20,000 operations; fully enclosed, maintenance-free, with a service life of up to 30 years.

Modular unit design concept allows direct removal and replacement of a faulty middle cabinet in special failure scenarios.

Product Parameters

No.

Project

Unit

Parameters

No.

Project

Unit

Parameters

1

Rated voltage

kV

12

10

insulating medium

/

SF₆

2

Rated current

A

1250, 2500, 3150, 4000

11

Arc grade

/

BFLR25, 31.5, 40KA,1S

3

Power frequency withstand voltage

To ground and interphase

kV

42

12

Annual leakage rate

%

≤ 0.05

Fracture

48

4

Lightning impulse withstand voltage

To ground and interphase fracture

kV

75

13

Mechanical life

Times

Circuit breaker: 10000 three position: 5000

85

5

Partial discharge

pC

<10

14

Rated inflation pressure (20 ℃)

Mpa

0.02

6

Rated short-circuit breaking current

kA

25, 31.5, 40

15

Minimum functional pressure

MPa

0

7

Rated short-circuit current breaking times

Times

30

16

Protection level

Cabinet body/gas box

IP4XIP67

8

Rated short-time withstand current/time

kA/s

25, 31.5, 40/4

17

Weight

kg

800, 1200, 1500, 1800

9

Rated peak withstand current

kA

63, 80, 100

18

Overall dimension (W×D×H) mm

1250A

2500A

3150A

4000A

500/900/900/1000 × 1300/1800/1800/1800 × 2400