The 12kV modular dual isolation dry air insulated ring main unit adopts a main circuit arrangement with dual isolating switches on the busbar side and line side, combined with an independent fast grounding switch, featuring a novel structure and a wide range of main wiring scheme applications. This product is primarily used in three-phase AC 50Hz, rated voltage 12kV secondary distribution systems. It is particularly suitable for compact secondary substations, switching stations, industrial and mining enterprises, urban residential communities, airports, railways, tunnels, high-rise buildings, and other power systems for receiving and distributing electric energy.

Main Technical Features:

Adopts integrated upper and lower direct-acting isolating switches with encapsulated pole units, combining the advantages of both upper and lower isolation schemes, offering broad scheme adaptability.

Circular conductor with uniform electric field; isolating contacts use spring contact fingers and high-precision positioning design to ensure long-term reliable contact.

Gas tank protection rating of IP67, fully shielded busbar expansion, verified for use at altitudes up to 5000m.

Uses pure dry air insulation and vacuum arc extinction, aligning with the "carbon peak and carbon neutrality" goals.

Based on simulation optimization, high insulation margin, with overall partial discharge ≤ 10pC.

Employs laser welding and helium leak detection to achieve an extremely low gas leakage rate.

Dual isolation break visualization enhances operational safety.

Maintenance-free, convenient for operation and maintenance, requiring no gas monitoring or recovery operations.

Product Parameters

No.

Project Name

Unit

Parameters

1

Rated voltage

kV

12

2

Rated current

Circuit breaker cabinet

A

630

3

Rated short-time power frequency withstand voltage

Isolation, vacuum fracture

kV

48

Interphase, relatively

42

4

Rated lightning impulse withstand voltage (peak)

Isolation, vacuum fracture

kV

85

Interphase, relatively

75

5

Partial discharge level

pC

≤ 10

6

Annual leakage rate

%/year

≤ 0.1

7

Rated short-time withstand current of main circuit

kA

20

8

Rated peak withstand current of main circuit

kA

50

9

Rated short circuit duration of main circuit

S

4

10

Rated inflation pressure

MPa

0.02

Minimum functional pressure

0

11

Breaker mechanical life

Times

10000

12

Three-position switch mechanical life

Times

3000

13

Protection level

Gas box

/

IP67

Cabinet

IP4X

14

Insulating gas

/

dry air

15

Internal arc rating

/

AFLR

16

Internal arc current

kA

20

17

Internal arc time

S

0.5

18

Overall dimension (width x depth x height) mm

V cabinet

420x850x1950

PT cabinet

600x850x1950