40.5kV (SF6 Lower Isolation) Ring Main Unit
Negotiable
China
No.12 Hongtai Road, Huaming Street, Dongli District, Tianjin City
15822469629
Online Contact
Favorite
Product Introduction

The 40.5kV (SF6 Lower Isolation) ring main unit is designed for 40.5kV systems with SF6 gas insulation and a three-position line side scheme. The product is primarily used in ring network power supply for new energy applications (40.5kV wind power, photovoltaic prefabricated substations, offshore wind power units, compact underground substations, and integrated boosting equipment for energy storage). It is safe to use, unaffected by climate, easy to install, requires minimal maintenance, saves space, and offers high safety.

Main Technical Features:

Vacuum arc extinction, SF6 insulation.

Three-position switch on the line side, offering comprehensive, flexible, and versatile schemes with strong expandability, allowing left, right, or top expansion.

Excellent airtight performance with advanced process control, laser welding, and helium leak detection, achieving an annual gas leakage rate of ≤ 0.01%.

Long mechanical life: circuit breaker 10,000 operations, three-position switch 3,000 operations.

Gas tank protection rating of IP67, with fully shielded busbar expansion.

Wide range of applications, including 40.5kV wind power, photovoltaic prefabricated substations, offshore wind power towers, compact underground substations, and integrated boosting equipment for energy storage.

Product Parameters

No.

Project Name

Unit

Parameters

1

Rated voltage

kV

40.5

2

Rated current

Circuit breaker cabinet

A

630

3

Rated short-time power frequency withstand voltage

Isolation, vacuum fracture

kV

118

Interphase, relatively

95

4

Rated lightning impulse withstand voltage (peak)

Isolation, vacuum fracture

kV

215

Interphase, relatively

185

5

Partial discharge level

pC

≤ 30

6

Annual leakage rate

%/year

≤ 0.01

7

Rated short-time withstand current of main circuit

kA

20

8

Rated peak withstand current of main circuit

kA

50

9

Rated short circuit duration of main circuit

S

4

10

Rated inflation pressure

MPa

0.02

Minimum functional pressure

0

11

Breaker mechanical life

Times

10000

12

Three-position switch mechanical life

Times

3000

13

Protection level

Gas box

/

IP67

Cabinet

IP4X

14

Insulating gas

/

SF₆

15

Internal arc rating

/

AFLR

16

Internal arc current

kA

20

17

Internal arc time

S

0.5

18

Overall dimension (width x depth x height) mm

V cabinet

420x900x2290