12kV (SF6) Ring Main Unit (Box)
Negotiable
China
No.12 Hongtai Road, Huaming Street, Dongli District, Tianjin City
15822469629
Online Contact
Favorite
Product Introduction

The SF6 gas-insulated ring main unit used in 12kV distribution network systems features a compact structure, small footprint, and modular design. It offers reliable electrical and mechanical performance with a fully enclosed structure, ensuring operational reliability and personal safety. It is maintenance-free, with all components made from standard parts, and the combination of modular components widely meets the requirements of various design schemes.

Main Technical Features:

Flexible and Versatile Solutions, Strong Expandability

Single gas tank or multi-unit shared tank configurations allow flexible combinations, with options for left, right, or top expansion, and easy connection via busbar connectors.

Safe and Environmentally Friendly

Comprehensive "five-proof interlocking," high insulation performance, strong breaking capacity, excellent dynamic and thermal stability, reliable pressure relief channels, passing the 20kA/1s arc test, with an annual leakage rate of ≤0.05%.

Long Mechanical Life

Circuit breaker: 10,000 operations; three-position switch: 3,000 operations.

Compact Structure

Load switch cabinet / circuit breaker cabinet width can be 325, 375, or 420mm; voltage transformer cabinet: 600mm; metering cabinet: 750mm.

High Protection Rating

High-voltage live components are enclosed in a stainless steel tank, with the gas tank achieving an IP67 protection rating, realizing full insulation, full enclosure, and maintenance-free operation.

Intelligent Integration

When paired with DTU station terminals, it supports intelligent distribution network functions such as protection, three-remote operations, online monitoring, and fault handling.

Product Parameters

No.

Project Name

Unit

Parameters

No.

Project Name

Unit

Parameters

No.

Project Name

Unit

Parameter Value

1

Rated voltage

kV

12

6

Annual leakage rate

%/year

≤ 0.05

13

Protection level

Gas box

/

IP67

2

Rated current

Load switch cabinet, circuit breaker cabinet

A

630

7

Rated short-time withstand current of main circuit

kA

20/25

Cabinet

IP4X

Combined electrical cabinet

125

8

Rated peak withstand current of main circuit

kA

50/63

14

Insulating gas

--

SF₆

3

Rated short-time power frequency withstand voltage

Isolation, vacuum fracture

kV

48

9

Rated short circuit duration of main circuit

S

4

15

Internal arc rating

/

AFLR

Interphase, relatively

42

10

Rated inflation pressure

MPa

0.03

16

Internal arc current

kA

20

4

Rated lightning impulse withstand voltage (peak)

Isolation, vacuum fracture

kV

85

Minimum functional pressure

0

17

Internal arc time

S

1

Interphase, relatively

75

11

Breaker mechanical life

Times

10000

18

Overall dimension (width x depth x height) mm

V cabinet

420x750x1950

5

Partial discharge level

pC

≤ 10

12

Three-position switch mechanical life

Times

3000

PT cabinet

600x750x1950