12kV (Eco-friendly Upper Isolation) Ring Main Unit (Box)
Negotiable
China
No.12 Hongtai Road, Huaming Street, Dongli District, Tianjin City
15822469629
Online Contact
Favorite
Product Introduction

The eco-friendly gas-insulated ring main unit adopts a modular design concept, developed as a new generation of environmentally friendly gas-insulated metal-enclosed switchgear for distribution networks. It is suitable for 12kV/50Hz secondary distribution systems with a rated current of 1250A and below, used for receiving and distributing electric energy, fully complying with the State Grid's "Standardized Design and Customization Scheme for Ring Main Units."

Main Technical Features:

1.High Reliability/Safety

20kA/1s arc-resistant design; integrated switch design with a simple structure, visible breaks, reliable interlocking design, and safe operation.

2.Eco-friendly and Maintenance-free

Uses dry air insulation and vacuum arc extinction, aligning with the "carbon peak and carbon neutrality" goals, maintenance-free, and convenient for operation and maintenance.

3.3D Simulation and Optimized Design

Fully shielded design with uniform electric field, direct-acting three-position switch, insulation performance at zero gauge pressure, and overall partial discharge ≤ 10pC.

4.Strong Adaptability to All-weather Environments

All high-voltage live parts are sealed in the gas chamber, with a gas tank protection rating of IP67, fully shielded expandable busbar, and verified for use at altitudes up to 5000m.

5.Simple Operation and High Intelligence

The circuit breaker and three-position switch support both manual and electric operation functions, fully meeting the State Grid's "Standardized Design and Customization Scheme for Ring Main Units" requirements.

6.Long Mechanical Life

Circuit breaker: 10,000 operations; three-position switch: 5,000 operations.

Product Parameters

No.

Project Name

Unit

Parameters

No.

Project Name

Unit

Parameters

No.

Project Name

Unit

Parameter Value

1

Rated voltage

kV

12

6

Annual leakage rate

%/year

≤ 0.01

13

Protection level

Gas box

/

IP67

       

630

7

Rated short-time withstand current of main circuit

kA

20/25

Cabinet

IP4X

2

Rated current

Circuit breaker cabinet

A

1250

8

Rated peak withstand current of main circuit

kA

50/63

14

Insulating gas

--

Dry air

3

Rated short-time power frequency withstand voltage

Isolation, vacuum fracture

kV

48

9

Rated short circuit duration of main circuit

S

4

15

Internal arc rating

/

AFLR

Interphase, relatively

42

10

Rated inflation pressure

MPa

0.03

16

Internal arc current

kA

20

   

Isolation, vacuum fracture

 

85

Minimum functional pressure

0

17

Internal arc time

S

1

4

Rated lightning impulse withstand voltage (peak)

Interphase, relatively

KV

75

11

Breaker mechanical life

Times

10000

18

Overall dimension (width x depth x height) mm

V cabinet

420x850x1950

500x944x1950

5

Partial discharge level

pC

≤ 10

12

Three-position switch mechanical life

Times

5000

PT cabinet

600x850x1950