FZRN21-40.5 Indoor High-Voltage Vacuum Load Switch
Negotiable
China
No.3, 22nd Street, Eastern New District, Wenling City, Taizhou City, Zhejiang Province
010-83910265
Online Contact
Favorite
Product Introduction

The FZRN21-40.5 high-voltage vacuum load switch and combined electrical apparatus are designed for three-phase AC 40.5kV, 50Hz power systems. They are used in conjunction with power equipment, ring main units (RMUs), and compact substations, and are widely applied in wind power generation, urban grid construction and renovation projects, industrial and mining enterprises, high-rise buildings, and public facilities. These products serve as ring network power supply units or terminal equipment, performing functions such as power distribution, control, and protection. Their technical performance complies with GB16926-2009 High-voltage Alternating Current Load Switch-fuse Combinations and IEC420 AC High-voltage Load Switch-fuse Combinations.

This product features high breaking capacity, safety, reliability, long electrical lifespan, frequent operation capability, compact structure, small size, lightweight, and minimal maintenance requirements. It is capable of breaking rated current, overload current, and short-circuit current, as well as preventing equipment phase loss operation. The switch has a visibly isolated disconnection gap and is equipped with an earthing switch with closing capability and an electric spring mechanism, enabling remote control operation.

Product Parameters

No.

Item

Unit

Value

1

Rated voltage

kV

40.5

2

Rated frequency

Hz

50

3

Maximum Rated Current of Fuse

A

63

4

Insulation Level

1-minute power frequency withstand voltage

kV

Vacuum gap & phase-to-phase & phase-to-earth: 95kV; Isolation gap: 110kV

Lightning impulse withstand voltage

kV

Vacuum gap & phase-to-phase & phase-to-earth: 185kV; Isolation gap: 215kV

5

Rated peak withstand current

kA

50

6

Rated short time withstand current (4s)

kA

20

7

Rated active load breaking current

A

1250

8

Rated closed-loop breaking current

A

1250

9

Rated cable-charging breaking current

kA

21

10

Rated short-circuit breaking current

kA

31.5

11

Rated transfer current

A

1700

12

Fuse type designation

A

XRNT3A-40.5/□-31.5

13

Striker energy output of fuse

A

2~5

14

Rated short circuit making current

kA

80 (Prospective Peak)

15

Rated peak withstand current of earthing switch

kA

50

16

Rated short-time withstand current of earthing switch (4s)

kA

20

17

Rated auxiliary circuit voltage (DC or AC)

V

220;110

18

Mechanical life

Times

10000