HXGN26-40.5 Ring Main Unit AC Metal-enclosed Switchgear
Negotiable
China
No.28 Yaoxi Road, Nanyu Town, Minhou County, Fuzhou City, Fujian Province
13763839179
Online Contact
Favorite
Product Introduction

This product is suitable for indoor three-phase AC 50Hz, rated voltage 40.5kV ring network power supply systems, mainly used in wind power generation, substations, industrial and mining enterprises, and high-rise buildings for receiving and distributing electrical energy, as well as for circuit protection, control, and monitoring.

Main Features:

Designed and manufactured using advanced foreign technology

Compact ring main unit that can be placed in box-type substations or directly inside wind turbine towers

SF6 ring main unit with no chopping overvoltage and stable breaking performance

Can be equipped with multiple cable groups, facilitating easy connection and installation

Cabinet side features an observation hole (with anti-misoperation function) for viewing the grounding knife position and status

Enclosure made of imported aluminum-zinc coated sheet, with strong corrosion resistance, suitable for harsh environments

Equipped with complete mechanical "five-prevention" interlocks, ensuring safe, reliable operation and convenient handling

Main component—FL(R)N44A load switch is a three-position integrated unit, allowing fuse replacement without power interruption on the incoming side, facilitating user maintenance

SF6 load switch adopts direct-acting compressed air arc extinguishing, with simple structure and compact size

Arc chamber made of stainless steel plate, formed in one step using special ribbing process and dedicated molds for high strength; welded by robotic welder for excellent sealing, corrosion resistance, and suitability for harsh environments

ZN91 vacuum circuit breaker offers high reliability and is especially suitable for frequent operations

Product Parameters

Project

Unit

HXGN26-40.5(Z)-with ZN91 circuit breaker

HXGN26-40.5(F)-with FLN44A load switch

HXGN26-40.5(F, R)-with FLRN44A combination

Rated voltage

kV

40.5

Rated 1min power frequency withstand voltage

kV

95

Rated lightning impulse withstand voltage (peak)

kV

185

Auxiliary and control loop power frequency withstand voltage

V

2000

Rated frequency

Hz

50

Rated current

A

1250~2500

400630

50,63,80

Rated active load breaking current

A

-

400630

-

Rated closed-loop breaking current of distribution line

A

-

400630

-

Rated cable charging breaking current

A

21

21

--

Rated no-load transformer breaking current

A

--

4

 

Rated short-time withstand current

kA

2531.5

12.5,16

-

Rated short circuit duration

S

4

3

-

Rated peak withstand current

kA

6380

31.5,40

 

Rated short-circuit breaking current

kA

2531.5

-

31.5 (expected value)

Rated short-circuit closing current

kA

6380

31.5,40

80 (expected value)

Rated transfer current or handover current

A

-

-

450800

Mechanical life

Times

20000

5000

Rated pressure of SF6 gas (gauge pressure at 20℃)

MPa

-

0.05

SF6 gas minimum functional pressure (gauge pressure at 20℃)

Mpa

-

0.03

Annual leakage rate of SF6 gas

-

-

≤ 1%