Vacuum Ring Main Unit

Negotiable
China
Room 908, 9th Floor, Building 1, Yard 2, Jinze West Road, Fengtai District, Beijing, 100073, P.R. China
15210760531
+86 18910035135
Online Contact
Favorite
Product Introduction

HXGN□-12 Vacuum Ring Main Unit (Cabinet) is suitable for industrial and mining enterprises, residential communities, high-rise buildings, and school power distribution systems. It serves as an indoor 10kV AC, 50Hz ring main unit power supply unit and terminal distribution equipment. It can break or close rated load current and transformer no-load current, and is capable of breaking or closing capacitive currents from overhead lines, cable lines, or capacitor banks over a certain distance. It is used in power systems for protection of distribution equipment, power distribution, and transformer protection control.

Key Features

Cabinet body is made of cold-rolled steel sheet or aluminum-zinc coated sheet through bending, offering robust structure, excellent sealing, and IP3X enclosure protection rating

The ring main unit is designed with two completely isolated upper and lower metal compartments: busbar compartment and switch compartment, eliminating the need for additional partition plates and facilitating safe maintenance and fuse replacement

The busbar compartment is fully metal-enclosed; busbars are connected via wall bushings. Upon request, a fully isolated instrument compartment can be installed in front of the busbar compartment for secondary equipment

The switch compartment mainly houses primary equipment and cable connections

Cabinet door and switch are mechanically interlocked for simple and reliable operation; the door is equipped with an observation window for viewing the isolating break and checking operating status

The high-voltage load switch cabinet is divided into cable compartment, busbar compartment, and instrument compartment. The front door is equipped with an interlocking device: only after high voltage is disconnected and the earthing switch is closed can the front and rear doors be opened.

Product Parameters

Project

Unit

Parameters

Rated voltage

kV

12

Rated frequency

Hz

50

Rated current of main bus

A

630

Rated short-time withstand current

kA/s

20/4

Rated peak withstand current

kA

50

Rated short-time closing current

kA

50

Rated active load breaking current

A

630

Rated closed-loop breaking current

A

630

Rated cable charging current

A

10

Rated short-circuit breaking current (circuit breaker)

kA

20

Rated transfer current

A

1750

Power frequency withstand voltage

kV

42/48

lightning impulse voltage

kV

75/85

Mechanical life (times)

Times

10,000

Technical parameters

Applicable environment

Maximum temperature: +60 ℃

Minimum temperature:-40 ℃

Relative humidity: daily average not more than 95%, monthly average not more than 90%

Seismic grade: 8