The centralized water metering solution uses wired remote-transmission water meters combined with battery-powered (or mains-powered) concentrators, providing a stable and efficient comprehensive remote meter-reading solution for high-density centralized metering scenarios. The water meters adopt high-precision mechanical base meters to collect flow data and support multiple electromechanical conversion methods such as photoelectric direct reading and non-magnetic pulse, meeting data acquisition requirements in various application scenarios. Depending on the number of connected water meters, a battery-powered concentrator (supporting 30+ ) or mains-powered concentrator (supporting 800+) can be selected to upload the data from all connected meters to the enterprise water management platform.
Centralized Water Metering Solution
Technical parameters
Flow parameters
|
Caliber DN |
Q3 /Q1 |
Overload flow Q4 |
Common flow Q3 |
Demarcation flow Q2 |
Minimum flow Q1 |
Min Reading |
Max Reading |
|
m3 /h |
L/h |
m3 |
|||||
|
15 |
160 |
3.125 |
2.5 |
25.0 |
15.6 |
0.00005 |
9 999 |
|
125 |
32.0 |
20.0 |
|||||
|
100 |
40.0 |
25.0 |
|||||
|
20 |
160 |
5 |
4.0 |
40.0 |
25.0 |
||
|
125 |
51.2 |
32.0 |
|||||
|
100 |
64.0 |
40.0 |
|||||
|
25 |
160 |
7.875 |
6.3 |
63.0 |
39.4 |
||
|
125 |
80.6 |
50.4 |
|||||
|
100 |
100.8 |
63.0 |
|||||
|
32 |
160 |
12.5 |
10 |
100.0 |
62.5 |
||
|
125 |
128.0 |
80.0 |
|||||
|
100 |
160.0 |
100.0 |
|||||
|
40 |
160 |
20 |
16 |
160.0 |
100.0 |
99 999 |
|
|
125 |
204.8 |
128.0 |
|||||
|
100 |
256.0 |
160.0 |
|||||
|
50 |
160 |
31.25 |
25 |
250.0 |
156.3 |
||
|
125 |
320.0 |
200.0 |
|||||
|
100 |
400.0 |
250.0 |
|||||
Maximum allowable error: the maximum allowable error in the low area (Q1 ≤Q<Q2) is ± 5%; the maximum allowable error in the high area (Q2 ≤Q≤ Q4) is ± 2%;
Note: LXSY-15F ~ 32F maximum reading is 99 999
Appearance size
Note: The dimensions and weight are for reference only, and the actual product shall prevail.
Rotor multi-stream dry direct-reading remote water meter
LXSY-15EZ6 ~ 50EZ6 LXSY-15EZ ~ 20EZ LXSGY-15GL ~ 25GL
|
Caliber DN |
Long L |
Width B |
High H |
Connection mode |
Weight |
|
|
mm |
d |
D |
Kg |
|||
|
Horizontal |
||||||
|
15 |
165 |
90 |
115 |
R1/2 |
G3/4B |
1.2 |
|
20 |
195 |
90 |
115 |
R3/4 |
G1B |
1.3 |
|
25 |
225 |
97 |
123 |
R1 |
G11/4B |
1.8 |
|
32 |
230 |
104 |
137 |
R11/4 |
G11/2B |
2.7 |
|
40 |
245 |
114 |
152 |
R11/2 |
G2B |
3.4 |
|
50 |
280 |
125 |
168 |
① |
4.7 |
|
|
Vertical |
||||||
|
15 |
137 |
89 |
100 |
R1/2 |
G3/4B |
1.4 |
|
20 |
138 |
95 |
100 |
R3/4 |
G1B |
1.7 |
|
25 |
145 |
97 |
110 |
R1 |
G11/4B |
2.5 |
|
Flange connection as per GB/T17241.6-2008/XG1-2011D = φ165 D1 = φ125 |
||||||
Rotor multi-beam wet detachable remote water meter
LXSY-15F ~ 32F
|
Caliber DN |
Long L |
Width B |
High H |
Connection mode |
Weight Kg |
|
|
mm |
d |
D |
||||
|
Horizontal |
||||||
|
15 |
165 |
138 |
138 |
R1/2 |
G3/4B |
1.5 |
|
20 |
195 |
139.5 |
139.5 |
R3/4 |
G1B |
1.8 |
|
25 |
225 |
146 |
146 |
R1 |
G1 1/4B |
2.2 |
|
32 |
230 |
146.5 |
146.5 |
R1 1/4 |
G1 1/2B |
2.5 |
Rotor multi-stream dry direct-reading remote valve-controlled water meter
LXSGF-15G ~ 25G LXSGF-15GL ~ 25GL
|
Caliber DN |
Long L |
Width B |
High H |
Connection mode |
Weight |
|
|
mm |
d |
D |
Kg |
|||
|
Horizontal |
||||||
|
15 |
165 |
106 |
125 |
R1/2 |
G3/4B |
1.5 |
|
20 |
195 |
106 |
125 |
R3/4 |
G1B |
1.8 |
|
25 |
225 |
107 |
137 |
R1 |
G11/4B |
2.2 |
|
Vertical |
||||||
|
15 |
181 |
99 |
130 |
R1/2 |
G3/4B |
1.8 |
|
20 |
181 |
99 |
130 |
R3/4 |
G1B |
2.1 |
|
25 |
186 |
107 |
155 |
R1 |
G11/4B |
2.7 |
Performance parameters
|
Temperature Class |
T30 |
Environmental grade |
Level O |
|
Pressure rating |
MAP16 |
Electromagnetic environment level |
Level E2 |
|
Pressure loss rating |
Δp63 |
Accuracy class |
Level 2 |
|
Flow field sensitivity level |
U0/D0 |
||
|
Communication mode |
M-Bus |
RS-485 |
|
|
Operating voltage |
Empty: the bus voltage is greater than 12V; Transmitting signal: the bus voltage is> 10V and <42V when the bus voltage is higher than the bus voltage when the signal is empty |
7.5-18V |
|
|
Standby current |
≤ 1mA |
≤ 3mA |
|
|
Baud rate |
2400bps or custom can be set |
2400bps or custom can be set |
|
|
Communication distance |
1000m (typical) |
500m (typical) |
|
|
Connection Method of Water Meter and System Bus |
Red and black |
Red Power (+) Blue RS-485 B- Yellow RS-485 A + Black power supply (GND) |
|