The DDZY188-Z adopts the most advanced dedicated integrated circuits for energy meters, microprocessors, non-volatile memory for permanent data storage, wide-temperature LCD display technology, and SMT manufacturing processes. It is a high-precision, wide-load-range, high-sensitivity, low-power-consumption AC energy meter. This smart meter accurately measures active energy in both forward and reverse directions, as well as energy consumption under different tariffs. It features forward and reverse active power measurement capabilities and performs real-time measurement and processing of electrical parameters including active power, voltage, current, power factor, and frequency. The meter supports time-of-use (TOU) metering, automatic meter reading, data storage for energy consumption, load profile recording, event logging, and other advanced functions.
DDZY188-Z Single-phase Prepaid Smart Energy Meter
Function Description
|
Electricity and freezing |
Measurement of combined active power, forward active power and reverse active power |
|
Instantaneous Freeze, Time Zone Table Switch Freeze, Day Time Table Switch Freeze |
|
|
Minute Freeze, Settlement Date Freeze, Hour Freeze, Day Freeze, Month Freeze |
|
|
Fee Control |
SM1 encryption algorithm, pre-alarm, pull-off and other functions |
|
Event Logging |
Time Table Programming Record, Time Zone Table Programming Record, Settlement Day Programming Record |
|
Ordinary time-calibration record, broadcast time-calibration record, programming record, zero-clearing record, power-down record and overcurrent record |
|
|
Key update record, pull switch record, zero line current abnormal record, metering chip fault record |
|
|
Record of misoperation of load switch, abnormal power supply, meter cover and clock failure |
|
|
Communication and Pulse |
RS485 communication, infrared communication, carrier module communication, wireless module communication |
|
LED pulse, electrical pulse output, clock signal output |
Technical indicators
|
Reference voltage |
220V |
|
|
Current specifications |
0.25-0.5(20)A,0.25-0.5(30)A, 0.25-0.5(40)A, 0.25-0.5(60)A, 0.5-1.0(40)A, 0.5-1.0(50)A, 0.5-1.0(60)A, 0.5-1.0(80)A, 0.5-1.0(100)A, 0.75-1.5(60)A, 1.0-2.0(80)A, 1.0-2.0(100)A |
|
|
Reference frequency |
50 Hz |
|
|
Accuracy class |
0.9Un ~ 1.1Un0.9Un ~ 1.1UnA Class B |
|
|
Starting current |
0.0021b, 0.004lb |
|
|
Environmental conditions |
Prescribed work |
-25 ℃ ~ 55 ℃ |
|
Extreme work |
-40 ℃ ~ 70 ℃ |
|
|
Storage and Transportation Limits |
-40 ℃ ~ 70 ℃ |
|
|
Limit working range |
0.0Un ~ 1.15Un |
|
|
Ambient relative humidity |
45% to 75% |
|
|
Operating voltage range |
Scope of Work |
0.9Un ~ 1.1Un |
|
Extended Scope of Work |
0.8Un ~ 1.15Un |
|
|
Limit working range |
0.0Un ~ 1.15Un |
|
|
Power consumption |
When there is no communication, the active power of the voltage line is ≤ 1.5W, and the apparent power is ≤ 8VA; during communication, the active power of the voltage line is ≤ 3W |
|
|
Battery |
Clock battery can be replaced, using green environmental protection lithium battery, battery capacity ≥ 1200mAh. After power failure, the program and clock in the electric energy meter can be maintained to work correctly for not less than 5 years. |
|
|
Antistatic ability |
> 15kV |
|
|
Design service life |
≥ 16 years |
|
|
Weight |
About 0.5kg |
|