DTZM188-Z Three-phase Four-wire Smart Energy Meter
Negotiable
China
No.26 Fengwan Road, Cicheng Town, Jiangbei District, Ningbo City, Zhejiang Province
+86 400 8227776
Online Contact
Favorite
Product Introduction

The three-phase IoT smart energy meter (hereinafter referred to as the energy meter) adopts a modular design, mainly consisting of three parts: metering module, management module, and expansion module.

The metering module consists of a signal processing unit, metering unit, and storage unit. It implements statutory metering functions and serves as the module for data interaction with the management module.

The management module consists of a data processing unit, display unit, security unit, storage unit, and control unit. It implements functions such as display, external communication, event recording, data freezing, and load control. It acts as middleware connecting the metering module and the expansion module.

The expansion module is used for business expansion of the energy meter, including extensions for communication, computation, monitoring, control, and other functions.

Product Parameters

Function Description

Electricity and freezing

Measurement of combined active power, forward active power and reverse active power

Instantaneous Freeze, Time Zone Table Switch Freeze, Day Time Table Switch Freeze

Minute Freeze, Hour Freeze, Day Freeze, Month Freeze, Settlement Date Freeze

Fee Control

Remote tripping, alarm and power protection command

Breaker Bluetooth automatic pairing

Event Logging

Loss of voltage, undervoltage, overvoltage, phase failure, overcurrent, current interruption, current loss event, voltage, current harmonic total distortion rate overrun event, demand overrun event, management module power-down event, module change event, clock fault event, terminal block overheat alarm event, terminal block temperature drastic change event, terminal block temperature imbalance event

Programming record, zero clearing record, key update record, pull-on record, load switch misoperation record, constant magnetic field record interference, metering chip failure record, interference, metering chip failure record, zero line current abnormal event, time schedule programming record, time zone schedule programming record, settlement date programming record, general timing record, broadcast timing record, management module plug-in event, meter cover open record

Communication and Pulse

Carrier module communication, wireless module communication, Bluetooth communication, load identification module communication, power quality module communication

LED pulse

Technical indicators

Accuracy Class

Active power: Class B, Class C, Class D (optional according to specifications)

Reactive: Class 2

Nominal voltage

Direct access type: 3x200/380V

Access via transformer: 3x5.7/100V-3x 100V

Current specifications

Direct Access: 0.4-1(100)A

Access via transformer: 0.015-0.075(6)A;0.003-0.015(1.2)A

Starting current

Grade B: 0.04ltr

Class C direct access type: 0.04ltr

Class C via transformer access type: 0.02ltr

Nominal frequency

50Hz

Ambient temperature

Reference temperature is 23 ℃

The specified working range:-25 ℃ ~ 55 ℃

Limit working range:-40 ℃ ~ 70 ℃

Storage and transportation conditions:-40 ℃ ~ 70 ℃

Relative humidity

45% to 75%

Communication Interface

Both Type A and Type B expansion modules are supported

Voltage line power consumption

Non-communication: active power ≤ 1.5W

apparent power ≤ 6VA; during communication

Active power of voltage line ≤ 8W

Current Line Power Consumption

10ltr<10A:0.2VA;10ltr ≥ 10A:≤ 0.4VA

Clock accuracy

≤ ± 0. 5S/24h(23 ℃),≤ ± 1s/24h(-25 ℃ ~ +55 ℃)

Battery voltage

Clock battery: 3.6V

Design service life

≥ 16 years

Weight

About 1.7kg

Overall dimension

290mm (high) x170mm (wide) x85mm (thick)