The smart energy meter is developed as a new-generation product in accordance with the overall requirements of the State Grid Corporation of China for building a "unified and robust smart grid," based on the State Grid's series standards for smart meters. This smart energy meter accurately measures active energy in both forward and reverse directions, energy consumption under different tariffs, and reactive energy in all four quadrants. It features recording of maximum active demand in both forward and reverse directions. It performs real-time measurement and processing of electrical parameters including active/reactive power, voltage, current, power factor, and frequency. The meter supports time-of-use (TOU) metering, automatic meter reading, data storage for energy consumption and demand, load profile recording, event logging, and other advanced functions.
DTZY188-Z Three-phase Four-wire Prepaid Smart Energy Meter
Function Description
|
Electric energy |
Electric energy metering |
|
Function |
Backlight, alarm, communication, programming, double rate, data display, power freezing, power failure wake-up, multi-level password management of broadcast time adjustment, multi-function detection Output port, communication relay alarm signal output, auxiliary power supply |
|
Event Logging |
Voltage qualification rate record, undervoltage record, loss of voltage record, total loss of voltage record, phase failure record |
|
Current interruption record, overload record, current loss record, current imbalance record, maximum demand record, overcurrent record |
|
|
Voltage/current reverse phase sequence record, total power factor exceeding lower limit record, programming record, power-down record, timing record, complete event record, load curve record, meter reset record and demand reset record |
|
|
Complete event record, event zero record, open table cover record, open button cover record |
|
|
Communication and Pulse |
RS485 communication, infrared communication, carrier module communication, wireless module communication |
|
LED pulse, electrical pulse output, clock signal output |
Technical indicators
|
Accurate grade |
Active power: Class B and Class C; |
|
Reactive: Class 2 |
|
|
Nominal voltage |
Direct access type: 3x20 0/380V |
|
Access via transformer: 3x5.7/100V;3x100V |
|
|
Current specifications |
Direct access: 0.2-0.5(60)A;0.4-1(100)A |
|
Connected via transformer: 0.015-0.075(6)A |
|
|
Starting current |
Grade B: 0.04ltr |
|
Class C direct access type: 0.04ltr |
|
|
Class C via transformer access type: 0.02ltr |
|
|
Nominal frequency |
50Hz |
|
Ambient temperature |
Reference temperature is 23 ℃ |
|
The specified working range:-25 ℃ ~ 55 ℃ |
|
|
Limit working range:-40 ℃ ~ 70 ℃ |
|
|
Storage and transportation conditions:-40 ℃ ~ 70 ℃ |
|
|
Relative humidity |
45% to 75% |
|
Communication Interface |
1-way standard RS485, 1-way remote infrared interface, channels are independent of each other |
|
Voltage line power consumption |
Non-communication: active power ≤ 1.5W; |
|
apparent power ≤ 6VA; |
|
|
During communication, the active power of the voltage line shall be ≤ 8W. |
|
|
Current Line Power Consumption |
10ltr<10A:≤ 0.2VA;10ltr ≥ 10A:≤ 0.4VA |
|
Clock accuracy |
≤ ± 0. 5S/24h(23 ℃),≤ ± 1s/24h(-25 ℃ ~ +55 ℃) |
|
Battery voltage |
Clock battery: 3.6V; Stop battery: 6V |
|
Design service life |
≥ 16 years |
|
Weight |
About 1.7kg |
|
Overall dimension |
290mm (high) x170mm (wide) x85mm (thick) |