Rated Power Voltage Combination and Tapping Range Connection Symbol Impedance Voltage No-load Loss (kW) Load Loss (kW) No-load Current (%) Weight (KG) Dimensions (mm)
(L×W×H)
Center Distance (mm)
HV M Body Oil Total
4000 110       121
±5%
or
±2×2.5%

6,

6.3,

10,

10.5,

11

YNd11 10.5 5.50 26.00 0.90 6400 4800 15600 4800×3800×4200 1475x1475
5000 5.60 28.00 0.90 6800 5200 16800 5050×3800×4225
6300 7.40 35.00 0.85 8100 5250 19800 5100×3980×4310
8000 8.90 42.00 0.70 9010 5500 21600 4960×3990×4300
10000 10.50 50.00 0.65 10600 5600 22760 5200×4000×4400
12500 12.40 59.00 0.65 12400 5840 24800 5200×4300×4580
16000 15.00 73.00 0.60 14500 6580 27600 5300×4580×4710
20000 17.60 88.00 0.45 17120 7800 35100 5330×4700×4900
25000 20.80 104.00 0.40 19840 7920 37300 5660×4800×4920 2040x1475
31500 24.60 123.00 0.30 23400 8900 42500 5720×4820×5010
40000 29.40 148.00 0.25 28800 10350 50600 5600×4860×5400
50000 35.20 175.00 0.20 34200 11600 61500 6200×4800×4900
63000 41.60 208.00 0.20 40200 12800 66700 6280×5040×5300