| S/N |
Name |
Unit |
FN12-12 FZN25-12 |
| 1 |
Rated voltage |
kV |
12 |
| 2 |
1 min power frequency withstand voltage |
kV |
Polar and interphase 42; Isolation fracture 48 |
| 3 |
Lightning impulse voltage (peak) |
kV |
Polar and interphase 75; Isolation fracture 85 |
| 4 |
Rated frequency |
Hz |
50 |
| 5 |
Rated current of the main busbar |
A |
630 |
| 6 |
Rated current |
A |
630 |
| 7 |
Load switch |
Electricalife under rated current |
Times |
Not less than 100 |
| 8 |
Power of breaking no-load transformer |
kVA |
1250 |
| 9 |
Rated thermal stability current |
kA |
20 / 4; Grounding switch 20 / 2 |
| 10 |
Rated dynamic stability current (peak) |
kA |
50 |
| 11 |
Rated short-circuit making current (peak) |
kA |
50 |
| 12 |
Composite apparatus |
Fuse rated current |
A |
100 |
| 13 |
Rated transfer current |
A |
1500 2000 |
| 14 |
Rated short-circuit breaking current |
kA |
31. 5 |
| 15 |
The model of the fuse used |
S |
S[]LAJ-12(XRNT-12) |
| 16 |
Mechanical life |
Times |
3000 10000 |
| 17 |
1min power frequency withstand voltage of auxiliary circuit |
kV |
2 |
| 18 |
Working voltage of electric operating mechanism |
V |
AC and DC 200; 110 |
| 19 |
Protection level |
|
IP4X |
| 20 |
Dimensions (WxD xH) |
mm |
650(850) × 900 × 2000(2200) 700(900) × 1000(900) × 2000(2200) |
Notes for ordering
The model, quantity, delivery date, and primary scheme number of the switchgear;
Primary system diagram, secondary schematic diagram, and arrangement diagram of switchgear;
The model and specifications of the rated current of the main busbar and primary components;
Special requirements (if any)