Hua-style box-type substation not only combines the miniaturization advantages of American-style box-type substations and the automation configuration advantages of European-style box-type substations, but also forms its unique safety, reliability, convenience and environmental protection characteristics. Hua-style box-type substations are particularly suitable for wind power and photovoltaic projects, fully demonstrating their application potential in the new energy field. The structure generally adopts a "品" shaped structure. The high-voltage side configuration of Hua-style box-type substations is different from that of American-style box-type substations. The high-voltage distribution room mainly uses air-insulated ring main units, which are equipped with many components such as disconnectors, vacuum circuit breakers, current transformers, zinc oxide arresters, cable heads, grounding switches and live display devices. On the low-voltage side, the configuration of Hua-style box-type substations is consistent with that of American-style and European-style box-type substations.

华式箱变

Product Parameters

10kV Photovoltaic Power Generation System

Item

Unit

High Voltage Unit

Transformer

Low Voltage Unit

Load Switch Fuse Combination / Vacuum Circuit Breaker

Rated Capacity

kVA

/

500~2000

/

Rated Voltage

kV

12

10/口

0.27~0.8

Rated Frequency

Hz

50

50

50

Rated Current

A

315

/

/

1min Power Frequency Withstand Voltage to Ground / Phase to Phase

kV

42/48

35

2.5

Lightning Impulse Withstand Voltage to Ground / Phase to Phase

kV

75/85

75/85 (Full Wave / Chopped Wave)

8

Rated Short-circuit Breaking Current

kA

25/31.5

/

/

Rated Peak Withstand Current

kA

31.5

/

75 (Ultimate Breaking)

Rated Short-time Withstand Current

kA

20

/

65 (Rated Breaking)

Rated Short-time Withstand Current Duration

s

4

/

/

Rated Short-circuit Making Current (Peak)

kA

50

/

 

Noise Level

dB

/

≤60

/

Enclosure Protection Degree

 

IP54

IP33

IP54

Overall Dimensions

According to the selected transformer capacity and actual high/low voltage configuration

 

35kV Photovoltaic Power Generation System

Item

Unit

High Voltage Unit

Transformer

Low Voltage Unit

Load Switch Fuse Combination / Vacuum Circuit Breaker

Rated Capacity

kVA

/

500~8000

/

Rated Voltage

kV

40.5

35/口

0.27~0.8

Rated Frequency

Hz

50

50

50

Rated Current

A

/

/

/

1min Power Frequency Withstand Voltage to Ground / Phase to Phase

kV

95/118

70

2.5

Lightning Impulse Withstand Voltage to Ground / Phase to Phase

kV

185/215

170/200 (Full Wave / Chopped Wave)

8

Rated Short-circuit Breaking Current

kA

31.5

25/31.5

 

/

Rated Peak Withstand Current

kA

63

63/80

/

75 (Ultimate Breaking)

Rated Short-time Withstand Current

kA

25

25/31.5

/

65 (Rated Breaking)

Rated Short-time Withstand Current Duration

s

2

4

/

/

Rated Short-circuit Making Current (Peak)

kA

63

63/80

/

 

Noise Level

dB

 

≤60

/

Enclosure Protection Degree

 

IP54

IP33

IP54

Overall Dimensions

According to the selected transformer capacity and actual high/low voltage configuration

Note: 口 is the system low-voltage inverter output voltage. Parameters are based on 1000m altitude for high voltage and 2000m altitude for low voltage as an example.

 

Wind Power Generation System

Item

Unit

High Voltage Unit

Transformer

Low Voltage Unit

Load Switch Fuse Combination

Rated Capacity

kVA

/

500~12500

 

Rated Voltage

kV

40.5

35/口

0.69~1.14

Rated Frequency

Hz

50

50

50

Rated Current

A

/

/

/

1min Power Frequency Withstand Voltage to Ground / Phase to Phase

kV

95/118

85

2.5/3.0

Lightning Impulse Withstand Voltage to Ground / Phase to Phase

kV

185/215

170/200 (Full Wave / Chopped Wave)

8/12

Rated Short-circuit Breaking Current

kA

31.5

25/31.5

/

/

Rated Peak Withstand Current

kA

63

63/80

/

75 (Ultimate Breaking)

Rated Short-time Withstand Current

kA

25

25/31.5

/

65 (Rated Breaking)

Rated Short-time Withstand Current Duration

s

2

4

/

1

Rated Short-circuit Making Current (Peak)

kA

63

63/80

/

 

Noise Level

dB

/

≤60

/

Enclosure Protection Degree

 

IP54

IP68

IP54

Overall Dimensions

According to the selected transformer capacity and actual high/low voltage configuration

Note: 口 is the system low-voltage inverter output voltage. Parameters are based on 1000m altitude for high voltage and 2000m altitude for low voltage as an example.