European-style Box-type Substation

Negotiable
China
No.1 Zhenxing Avenue, Shangyu District, Shaoxing City, Zhejiang Province
0575-89289448
Online Contact
Favorite
Product Introduction

European-style box-type substation mainly adopts a "目" shaped structure, integrating high-voltage and low-voltage switchgear with the transformer into one outdoor enclosure. Not only is the internal layout clear, but it also integrates many components such as conventional medium-voltage switchgear, ring main unit, low-voltage cabinet and transformer. Generally, dry-type transformers (a few use oil-immersed) are adopted, featuring advanced and reliable technology, factory prefabrication, high degree of automation, and flexible combination methods.

High-voltage schemes include split-type circuit breaker, integrated circuit breaker, gas-filled components, gas-filled cabinet and other options to meet various customer needs. Generally, dry-type transformers (a few use oil-immersed) are adopted, with reasonable protective structure, dust-proof structure and low-temperature resistance, anti-exposure, anti-corrosion, anti-sand, rain-proof, and can meet the requirements of safe operation in harsh environments. Advanced and reliable technology, factory batch production, high degree of automation, flexible combination methods and other characteristics.

欧式箱变

Product Parameters

10kV Photovoltaic Power Generation System

Item

Unit

High Voltage Unit

Transformer

Low Voltage Unit

Load Switch Fuse Combination / Vacuum Circuit Breaker

Rated Capacity

kVA

/

500~2000

/

Rated Voltage

kV

12

10/口

0.27~0.8

Rated Frequency

Hz

50

50

50

Rated Current

A

315

/

/

1min Power Frequency Withstand Voltage to Ground / Phase to Phase

kV

42/48

35

2.5

Lightning Impulse Withstand Voltage to Ground / Phase to Phase

kV

75/85

75/85 (Full Wave / Chopped Wave)

8

Rated Short-circuit Breaking Current

kA

25/31.5

/

/

Rated Peak Withstand Current

kA

31.5

/

75 (Ultimate Breaking)

Rated Short-time Withstand Current

kA

20

/

65 (Rated Breaking)

Rated Short-time Withstand Current Duration

s

4

/

 

Rated Short-circuit Making Current (Peak)

kA

50

/

 

Noise Level

dB

/

≤60

 

Enclosure Protection Degree

 

IP54

IP33

IP54

Overall Dimensions

According to the selected transformer capacity and actual high/low voltage configuration

 

35kV Photovoltaic Power Generation System

Item

Unit

High Voltage Unit

Transformer

Low Voltage Unit

Load Switch Fuse Combination / Vacuum Circuit Breaker

Rated Capacity

kVA

/

500~8000

/

Rated Voltage

kV

40.5

35/口

0.27~0.8

Rated Frequency

Hz

50

50

50

Rated Current

A

/

/

/

1min Power Frequency Withstand Voltage to Ground / Phase to Phase

kV

95/118

70

2.5

Lightning Impulse Withstand Voltage to Ground / Phase to Phase

kV

185/215

170/200 (Full Wave / Chopped Wave)

8

Rated Short-circuit Breaking Current

kA

31.5

25/31.5

 

/

Rated Peak Withstand Current

kA

63

63/80

/

75 (Ultimate Breaking)

Rated Short-time Withstand Current

kA

25

25/31.5

/

65 (Rated Breaking)

Rated Short-time Withstand Current Duration

s

2

4

/

/

Rated Short-circuit Making Current (Peak)

kA

63

63/80

/

 

Noise Level

dB

 

≤60

/

Enclosure Protection Degree

 

IP54

IP33

IP54

Overall Dimensions

According to the selected transformer capacity and actual high/low voltage configuration

Note: 口 is the system low-voltage inverter output voltage. Parameters are based on 1000m altitude for high voltage and 2000m altitude for low voltage as an example.