Type/Applications:

WYJZWFY4: Meet with requirements of pollution class IV
Max. system voltage: 362kV, applicable to 800~2500mm²
Max. system voltage: 550kV, applicable to 800~2500mm²

Features:

  • 1. Stress cone is injection-molded by excellent EPDM rubber. Secured by the spring cone carrier, our stress cone is designed with a stress cone cover so as to be isolated from insulated agent ensures excellent electrical property.
  • 2. Multi-layer sealing construction avoids water or oil leakage during operation and prolongs service life of termination.
  • 3. Rain sheds of various sizes on terminations well prevent pollution flashover.
  • 4. Outer insulation made of silicone rubber, outstanding in properties of anti-pollution flashover, anti-UV, anti-aging and anti-explosion while it weighs only 1/2 of porcelain termination at equivalent voltage level provides a more convenient installation.
  • 5. Type tested according to IEC 62067, GB/T 22078.
Product Parameters

Cable Lug Palm Specification of Composite Termination

Voltage rating Cable nominal cross-section Lug hole distance C(mm) Connecting hole of lug Q(mm) Palm width of cable lug D(mm) Palm length of cable lug L(mm)
362kV 800mm2 45 14 80 115
  1000-1600mm2 50 17 100 135
  2000-2500mm2 50 18 125 165
550kV 800mm2 45 14 80 115
  1000-1600mm2 50 17 100 135
  2000-2500mm2 50 18 125 165

Base Plate Mounting Dimension

Base Plate Mounting Dimension

Outline Dimension

Max. system voltage H (mm) A (mm) B (mm)
362kV 4038±10 4583±20 4944±50
550kV 5380±10 5295±20 6286±50

Notice When Ordering:

  • 1. Cable configuration and the cross-sectional area of earth wire shall be submitted when ordering.
  • 2. Feel free to contact our sales manager before ordering if you have any special requirements.