The BPK200-35/85-(10-n)Z series dry-type vacuum on-load tap-changer: This type of tap-changer is suitable for arc suppression coils with a rated voltage of 35kV and below, and a capacity of 4000kVA or less for single-phase dry-type on-load current regulation. BPK200-35/85-(10-n)Z, model designation: B→current of 750A/250A and below; P→vacuum contact switching; K→air insulation; 200→rated current; 35→voltage class; 85→maximum longitudinal insulation; (09-19)/(10-n)→maximum number of tap positions; Z→mid-point current regulation
On-load tap-changer
|
Item |
Parameter |
|||
|
Maximum operating voltage (kV) |
38.5 |
|||
|
Rated current (A) |
200 |
|||
|
Short-circuit withstand capability (kA) |
Thermal stability (2S) |
3 |
||
|
Dynamic stability (peak) |
7.5 |
|||
|
Frequency (Hz) |
50 or 60 |
|||
|
Step voltage (V) |
2000 |
|||
|
Step capacity (kVA) |
80 |
|||
|
Maximum number of tap positions |
10~17 positions |
|||
|
Time for one motor-driven operation per step |
Approx. 5 seconds |
|||
|
Time for one switching operation per step |
Approx. 60 milliseconds |
|||
|
Insulation to earth (kV) |
Rated power-frequency withstand voltage (50Hz/5min) |
85 |
||
|
Rated lightning impulse withstand voltage (1.2/50μs) |
200 |
|||
|
Internal insulation of the switch (kV) |
Rated power-frequency withstand voltage between adjacent taps (50Hz/5min) |
6 |
||
|
Rated lightning impulse withstand voltage between adjacent taps (1.2/50μs) |
18 |
|||
|
Rated power-frequency withstand voltage between maximum and minimum taps (50Hz/5min) |
28 |
|||
|
Rated lightning impulse withstand voltage between maximum and minimum taps (1.2/50μs) |
60 |
|||
|
Electrical life of contacts |
Greater than 100,000 operations |
|||
|
Mechanical life |
Greater than 800,000 operations |
|||
|
Operating frequency |
No less than 60 seconds per operation |
|||
|
Standard for switch manufacturing |
GB/T10230 IEC 60214 |
|||
|
Motor |
Power |
140W |
||
|
Voltage |
Single-phase 220V |
|||
|
Maximum current |
1.4A |
|||
|
Speed |
1300r/min |
|||
BPK200-35/85-(10-n)Z series dry-type vacuum on-load tap-changer