SYSRM16-12 Gas-Insulated (Fully Enclosed) Ring Main Unit

Negotiable
China
Building 2-33, Caicheng Industrial Park, Economic Development Zone, Shangrao City, Jiangxi Province
0793-8876066
Online Contact
Favorite

Product Introduction

Overview

The SYSRM16-12 gas-insulated SF6 metal-enclosed fully insulated ring main switchgear has passed the type test of the National High Voltage Apparatus Testing Center. It is widely used in 10kV/6kV power distribution systems and is the preferred switchgear product for various urban and rural user substations and distribution systems.

The switchgear adopts a modular unit design and can be combined according to different applications. It consists of two major categories: fixed unit combinations and extendable unit combinations, meeting the needs of various substations for flexible use of compact switchgear.

The SYSRM16-12 gas-insulated switchgear is a completely sealed system, with all live parts and switches enclosed in a stainless steel housing. The entire switchgear is unaffected by external environmental conditions, thereby ensuring operational reliability and personal safety, and achieving maintenance-free operation. By selecting extendable busbars, any combination can be realized, achieving full modularization. The extendable busbars are safely insulated and shielded, ensuring high reliability and safety. The SHSRM16-12 gas-insulated switchgear can also provide TV-based automation solutions, forming the concept of intelligent switchgear and minimizing on-site installation and commissioning workload.

The SYSRM16-12 gas-insulated switchgear is available in non-extendable standard configurations and extendable standard configurations. Due to the combinability of full modules and half modules as well as its own extendability, it offers extremely exceptional flexibility.

The SYSRM16-12 gas-insulated switchgear complies with GB standards. The design life exceeds 30 years under indoor conditions (40℃) and outdoor conditions (-50℃).

Performance Specifications

◆ SF6 gas pressure

◇ Absolute pressure at 20℃: 1.4 bar

◇ Annual gas leakage rate: 0.2%/year

◇ Protection degree: IP67

◇ Stainless steel thickness of gas compartment: 3.0mm

◆ Busbar

◇ Busbar inside switchgear: 400mm2Cu

◇ Earthing busbar of switchgear: 150mm2Cu

◆ Color

◇ Front panel of switchgear: RAL7012

◇ Side panels and front cover of cable compartment: RAL7035

◆ Normal operating environmental conditions

◇ Maximum temperature: 40℃

◇ Minimum temperature: -50℃

◇ Maximum average relative humidity: ≤95%

◇ Altitude: ≤2000m

◆ Compliant standards

GB/T11022 GB3906 GB1985

GB16926 GB38041 GB1984 GB3309

IEC60056 IEC60129 IEC60256

IEC60298 IEC60420 IEC60694

Technical Parameters

Name Unit C Module F Module V Module CB Module
Load Break Switch Combined Apparatus Vacuum Switch Disconnector/Earthing Switch Vacuum Circuit Breaker Disconnector/Earthing Switch
Rated voltage KV 12 12 12 12 12 12
Rated frequency HZ 50 50 50 50 50 50
Power frequency withstand voltage (phase-to-phase/breaking gap) kV 42/48 42/48 42/48 42/48 42/48 42/48
Lightning impulse withstand voltage kV 75/85 75/85 75/85 75/85 75/85 75/85
Rated current A 630 Note 1) 630 1250/630
Breaking capacity
Rated closed-loop breaking current A 630
Rated cable charging breaking current A 10
Rated short-circuit making current (peak) A 50 80
Rated peak withstand current kA 50
Rated short-time withstand current kA/3S 20 25
Rated short-circuit breaking current kA 31.5 20
Rated transfer current A 1700
Maximum current of associated fuse A - 125
Circuit resistance -n ≤300 ≤600
Mechanical life Operations 5000 3000 5000 2000 5000 5000

Note: 1) Depends on the current rating of the fuse