Overview
The GCS device is suitable for power distribution systems in power plants, petroleum, chemical, metallurgy, textile, high-rise building and other industries. In large power plants, petrochemical systems and other places with a high degree of automation that require computer interfaces, it serves as a low-voltage complete power distribution device for power distribution, centralized motor control, and reactive power compensation in power generation and supply systems with a three-phase AC frequency of 50(60)Hz, a rated operating voltage of 380V(400V), (660V), and a rated current of 4000A and below.
Basic Parameters
| Main circuit rated voltage (V) | AC 380(400), (660) | ||
| Auxiliary circuit rated voltage (V) | AC 220, 380(400) | DC 110/220 | |
| Rated frequency (Hz) | 50(60) | ||
| Rated insulation voltage (V) | 660(1000) | ||
| Rated current (V) | Horizontal busbar | ≤4000 | |
| Vertical busbar (MCC) | 1000 | ||
| Busbar rated short-time withstand current (kA/1s) | 50,80 | ||
| Busbar rated peak withstand current (kA/0.1s) | 105,176 | ||
| Power frequency test voltage (V/1min) | Main circuit | 2500 | |
| Auxiliary circuit | 1760 | ||
| Busbar | Three-phase four-wire system | A, B, C, PEN | |
| Three-phase five-wire system | A, B, C, PE, N | ||
| Protection degree | IP30, IP40 | ||