Gas alarm for household and small catering kitchens GTY-XH800
Negotiable
China
25-1 U Valley, Liandong, No. 19 Xiangfu Avenue, Shuangfu Street, Jiangjin District, Chongqing
+8619802396738
Online Contact
Favorite
Product Introduction

**Gas alarm for household and small catering kitchens**GTY-XH800

https://statics.wedoany.com/2024/0809/20240809033148589.png

 

- Modular design, easy to disassemble, load and replace;
- Over-range protection, LED display alarm to prevent sensor poisoning;
- Catalytic combustion sensor, stable operation and high reliability;
- The detector can be set, calibrated, self-tested and other operations through the infrared remote control.
- Terminal wiring is used for external interface, and installation and wiring are reliable and convenient;
- There are switch quantity and DC24V output, which can be linked to on-site equipment;
- It has local sound and light alarm function;

PERFORMANCE indicators

PERFORMANCE indicators

 

Detection of gas

Methane (CH4), propane (C3H8)

Display range

(3-100)%LEL

Power

 

Power

DC24V

≤ 3W

 

Detection principle

Catalytic combustion type

Sampling mode

Natural diffusion

Communication mode

Bus system (two buses)

Display mode

4 digit LED digital tube display concentration value

Alarm Setpoint

Low report: 20% LEL high Report: 50% LEL

Status indication

3 LED indications: power supply, fault, alarm (different status indicates different levels)

Alarm mode

Sound and light alarm

Sound alarm

About 100DB

Control output signal

2 (Level I alarm point, Level II alarm point)

Weight

≤ 2kg

Working temperature

-40 ℃ ~ 70 ℃

Working humidity

<95% RH without condensation

Pressure Limits

86kPa ~ 106kPa

Explosion-proof grade

Ex db IIC T6 Gb

Protection level

IP66

Response time

≤ 30s