Rated capacity kV · A |
Voltage combination level grading range |
Bonding Group Label |
No-load loss kW |
Load loss kW |
No-load current % |
Short circuit impedance % |
|
|
High pressure classification range kV |
Low voltage kV |
||||||
|
6300 |
110±8×1.25% |
6.3 6.6 10.5 21 |
Ynd11 |
4.4 |
32 |
0.64 |
10.5 |
|
8000 |
5.3 |
38 |
0.64 |
||||
|
10000 |
6.2 |
45 |
0.59 |
||||
|
12500 |
7.4 |
53 |
0.59 |
||||
|
16000 |
8.9 |
66 |
0.55 |
||||
|
20000 |
10.6 |
79 |
0.55 |
||||
|
25000 |
12.5 |
94 |
0.51 |
||||
|
31500 |
14.9 |
111 |
0.51 |
||||
|
40000 |
17.8 |
140 |
0.46 |
12 to 18 |
|||
|
50000 |
21 |
175 |
0.46 |
||||
|
63000 |
25 |
209 |
0.42 |
||||
|
Note 1: On-load voltage regulating transformer, temporarily provide step-down structure products. Note 2: According to user requirements, products with other voltage combinations can be provided. Note 3: The-10% tap position is the maximum current tap. Note 4: When the annual average load rate of the transformer is between 45% and 50%, the highest operating efficiency can be obtained by using the loss values in the table. |
|||||||