Rated capacity kV · A |
Voltage combination level grading range |
Bonding Group Label |
No-load loss kW |
Load loss kW |
No-load current % |
Short circuit impedance % |
||
|
High pressure classification range kV |
High pressure kv |
Low voltage kV |
||||||
|
30 |
±2×2.5±5 |
6 6.3 10 10.5 |
0.4 |
Dyn11 Yzn11 Yyn0 |
0.065 |
0.455/0.43 |
1.5 |
4 |
|
50 |
0.08 |
0.655/0.625 |
1.3 |
|||||
|
63 |
0.09 |
0.785/0.745 |
1.2 |
|||||
|
80 |
0.105 |
0.945/0.9 |
1.2 |
|||||
|
100 |
0.12 |
1.14/1.08 |
1.1 |
|||||
|
125 |
0.135 |
1.36/1.295 |
1.1 |
|||||
|
160 |
0.16 |
1.665/1.585 |
1 |
|||||
|
200 |
0.19 |
1.97/1.87 |
1 |
|||||
|
250 |
0.23 |
2.3/2.195 |
0.9 |
|||||
|
315 |
0.27 |
2.76/2.63 |
0.9 |
|||||
|
400 |
0.33 |
3.25/3.095 |
0.8 |
|||||
|
500 |
0.385 |
3.9/3.71 |
0.8 |
|||||
|
630 |
Dyn11 Yyn0 |
0.46 |
4.46 |
0.6 |
||||
|
800 |
0.56 |
5.4 |
0.6 |
4.5 |
||||
|
1000 |
0.665 |
7.415 |
0.6 |
|||||
|
1250 |
0.78 |
8.64 |
0.5 |
|||||
|
1600 |
0.94 |
10.44 |
0.5 |
|||||
|
2000 |
1.085 |
13.18 |
0.4 |
5 |
||||
|
2500 |
1.28 |
13.36 |
0.4 |
|||||
|
Note 1: For Transformers with rated capacity of 500kV·A and below, the load loss value above the slash in the table is applicable to Dynll or Yznll Connection Group, and the load loss value below the slash is applicable to Yyn0 connection group. Note 2: When the annual average load rate of the transformer is between 35% and 40%, the highest operating efficiency can be obtained by using the loss values in the table. |
||||||||