Rated capacity kV · A |
Voltage combination level grading range |
Bonding Group Label |
No-load loss kW |
Load loss kW |
No-load current % |
Short circuit impedance % |
||
|
High pressure classification range kV |
Medium Voltage kV |
Low voltage kV |
||||||
|
6300 |
110±8×1.25% |
36 37 38.5 |
6.3 6.6 10.5 21 |
YNyn0d11 |
5.3 |
40 |
0.76 |
High-Medium10.5 High-Low17.5-18.5 Medium-low 6.5 |
|
8000 |
6.3 |
48 |
0.76 |
|||||
|
10000 |
7.5 |
56 |
0.71 |
|||||
|
12500 |
8.9 |
67 |
0.71 |
|||||
|
16000 |
10.6 |
81 |
0.67 |
|||||
|
20000 |
12.5 |
95 |
0.67 |
|||||
|
25000 |
14.9 |
113 |
0.62 |
|||||
|
31500 |
17.7 |
134 |
0.62 |
|||||
|
40000 |
21.2 |
161 |
0.58 |
|||||
|
50000 |
25 |
192 |
0.58 |
|||||
|
63000 |
29.8 |
230 |
0.53 |
|||||
|
Note 1: On-load voltage regulating transformer, temporarily provide step-down structure products. Note 2: The capacity allocation of high, medium and low voltage windings is (100/100/100)%. Note 3: The label of the coupling group can be YNd11y10 as required. Note 4: The-10% tap position is the maximum current tap. Note 5: According to user requirements, the medium voltage can be different from the voltage value in the table or tap. Note 6: When the annual average load rate of the transformer is about 47%, the highest operating efficiency can be obtained by using the loss values in the table. |
||||||||