Rated capacity kV · A |
Voltage combination level grading range |
Bonding Group Label |
No-load loss kW |
Load loss kW |
No-load current % |
Short circuit impedance % |
||
|
High pressure classification range kV |
Medium Voltage kV |
Low voltage kV |
||||||
|
31500 |
220±8×1.25% 230±8×1.25% |
69 115 121 |
6.3 6.6 10.5 21 36 37 38.5 |
Ynyn0d11 |
19 |
138 |
0.63 |
High-Medium12 to 14 High-Low22-24 Medium-low7-9 |
|
40000 |
23 |
165 |
0.6 |
|||||
|
50000 |
26 |
194 |
0.6 |
|||||
|
63000 |
31 |
231 |
0.55 |
|||||
|
90000 |
40 |
300 |
0.44 |
|||||
|
120000 |
10.5 21 36 37 38.5 |
51 |
369 |
0.44 |
||||
|
150000 |
59 |
438 |
0.39 |
|||||
|
180000 |
68 |
538 |
0.39 |
|||||
|
240000 |
85 |
667 |
0.35 |
|||||
|
Note 1: The data listed in the table are applicable to step-down structure products, and step-up structure products can also be provided as required. Note 2: Low voltage 35kV transformers are also available upon request. Note 3: When the annual average load rate of the transformer is between 45% and 50%, the highest operating efficiency can be obtained by using the loss values in the table. |
||||||||


京公网安备 11010802043282号