BSM1 busway system possesses the common characteristics of BSM compact insulation busway series; the differences are: its conductor adopts T2 quality copper. loading area of the selected is rather large (approximate the loading area of thetraditional air busway system),therefore the electric resistance is small; the rise of temperature is low, its power consumption is small.
BSM1 series copper conductor denselyinsulated Busway
|
BSM1 BSM1 type busbar selection table |
||||
|
Mode |
BSM1/4P |
BSM1/5P |
||
|
Overall size |
W(mm) |
H(mm) |
W(mm) |
H(mm) |
|
400 |
120 |
110 |
120 |
110 |
|
500 |
120 |
125 |
120 |
125 |
|
630 |
120 |
125 |
20 |
125 |
|
800 |
120 |
160 |
20 |
160 |
|
1000 |
120 |
175 |
20 |
175 |
|
1250 |
120 |
175 |
120 |
175 |
|
1600 |
120 |
220 |
120 |
220 |
|
2000 |
120 |
270 |
120 |
270 |
|
2500 |
120 |
325 |
120 |
325 |
|
3150 |
120 |
325 |
120 |
325 |
|
4000 |
120 |
375 |
120 |
375 |
|
5000 |
120 |
375 |
120 |
375 |
|
BSM1 Technical parameters of BSM1 Bus duct |
||||||||||||
|
EXECUTIVE STANDARD IEC61439-1:2011 GB7251.1-2013 GB7251.6-2015 |
||||||||||||
|
Ambient temperature |
(℃) |
-5/+40(24H35℃) |
||||||||||
|
Altitude |
|
Up to 2000M |
||||||||||
|
Protective grade |
|
lp 40、54、65 |
||||||||||
|
Unit length |
(m) |
Optional among 1.62.53.26(0.5-6) |
||||||||||
|
Rated insulation voltage ul |
(V) |
660/1000 |
||||||||||
|
|
(V) |
380/660 |
||||||||||
|
Frequency |
(HZ) |
50-60 |
||||||||||
|
Rated current In |
(A) |
400 |
630 |
800 |
1000 |
1250 |
1600 |
2000 |
2500 |
3150 |
4000 |
5000 |
|
Resistance R20 |
(uΩ/ml) |
88.9 |
71.1 |
56.4 |
40.3 |
33.2 |
24.5 |
19.5 |
14.5 |
11.3 |
8.9 |
6.7 |
|
Reactance X20 |
(uΩ/m) |
66.5 |
62.2 |
39.1 |
37.9 |
46.6 |
30.1 |
7.4 |
25.9 |
25.3 |
14.3 |
13 |
|
Total reactance 720 |
(uΩ/m) |
290 |
276 |
184.2 |
176 |
221.6 |
150 |
131 |
130 |
121 |
76.2 |
69 |
|
|
(mV/m |
77.5 |
81 |
77.3 |
77.5 |
76.4 |
74.9 |
73.3 |
71.4 |
69.7 |
63 |
61.4 |
|
|
(KA) |
30 |
30 |
50 |
50 |
80 |
||||||
|
|
(KA) |
63 |
63 |
105 |
105 |
176 |
||||||
|
Temperature rise |
(K) |
≤70 |
||||||||||
|
Insulation resistance |
(MΩ) |
≥20 |
||||||||||
|
Electrical interval |
(mm) |
≥10 |
||||||||||
|
Creepage distance |
(mm) |
≥12 |
||||||||||
|
PE |
(Ω) |
<0.02 |
||||||||||
|
Dielectric property |
|
50Hz,3750V/Imin no breakdown or flashover |
||||||||||
|
Installation way |
|
Vertical or horizontal |
||||||||||
|
Quantity of plug port |
|
|
||||||||||
|
Maximum fixed interval |
(m) |
4 |
4 |
3 |
3 |
|||||||
|
Balance load |
(kg/m) |
20 |
20 |
25 |
30 |
|||||||
|
Centralized load |
(kg) |
90 |
90 |
90 |
90 |
|||||||