ZGS-12 American-style Pre-assembled Box-type Substation
Negotiable
China
Sanyu Village, Wengyang Subdistrict, Yueqing City, Wenzhou City, Zhejiang Province
+86 15286827607
Online Contact
Favorite
Product Introduction

Product Introduction:
This product is developed by absorbing foreign professional technologies and combining domestic practical conditions. It has the advantages of compact size, easy installation and maintenance, low noise, low loss, anti-theft, overload capacity, and full protection. It is suitable for new residential areas, green belts, parks, stations, hotels, construction sites, airports, and other locations.
The ZGS-12 series American-style pre-assembled box-type substation is suitable for 10kV ring network power supply, dual power supply, or terminal power supply systems, serving as a transformer, metering, compensation control, and protection device. This product meets the following standards: GB/T17467-1998 “High and Low Voltage Pre-assembled Substations”, and DL/T537-93 “6-35kV Box-type Substation Ordering Technical Conditions”.

Product Features:

Fully insulated, fully sealed, maintenance-free, and reliable in ensuring personal safety.

Compact structure, with volume only 1/3 to 1/5 of the same capacity European-type substations, and lower height.

Can adopt a modular structure to avoid contamination of transformer oil in the oil tank.

The high-voltage side uses double fuses for full-range protection, significantly reducing costs.

Can be used in both ring networks and as a terminal substation, with emergency plug-in capability for cable terminals at 200A load current.

The box body uses a honeycomb double-layer composite board, providing thermal insulation and heat dissipation functions.

The low-voltage side is equipped with an electronic phase loss protector, which can quickly disconnect the main incoming switch when abnormal voltage occurs in the system.

The high-voltage side uses oil-immersed load switches or SF6 load switches, which can be electrically upgraded to support distribution network automation.

Equipped with oil-immersed S9 or the higher-performance S11 series transformers.

Product Parameters

Technical parameters of load switch

Table 1: Technical Parameters of Pre-installed Substation

Serial Number

Name

Unit

Technical parameters

1

Rated voltage

kV

10/0.4 (high pressure/low pressure)

2

Maximum operating voltage

kV

12 (high pressure side)

3

Rated frequency

Hz

50

4

Rated capacity

kVA

50-1600

5

1m power frequency withstand voltage

kV

35

6

Lightning impulse voltage

kV

75

7

Cooling mode

-

Oil-immersed self-cooling

8

Breaking current of HV backup fuse

kA

50

9

Breaking current of plug-in fuse

kA

2.5

10

Ambient temperature

-35~+40

11

Allowable temperature rise of coil

k

65

12

No-load voltage regulation

-

± 5% or ± 2 × 2.5%

13

Noise level

dB

50

14

Protection level

-

IP43

Table 2: Technical Parameters of Fuse (Recommended Table for Selection and Configuration of Oil Diffuse Fuse of the Company)

The high-voltage side of American box transformer is provided with full-range protection by backup protection fuse and plug-in fuse in series, which is simple in principle, economical and reliable. The backup protection fuse is an oil-diffuse high-voltage current-limiting fuse with large breaking capacity and only operates when the transformer fails. The plug-in fuse is equipped with double-sensitive fuse, which can provide double protection of current and temperature. After the double-sensitive fuse is blown, the fuse core can be easily replaced on site.

Serial Number

Three-phase transformer capacity (kVA)

Transformer primary voltage (10kV)

XRNT Rated current (A)

Rated current of PRNT1 overload protection (A)

1

30

10

6

2

50

16

8

3

80

16

10

4

100

20

15

5

125

25

15

6

160

31.5

25

7

200

40

25

8

250

50

40

9

315

63

40

10

400

63

40

11

500

80

50

12

630

100

50, 65

13

800

125

65

14

1250

160

100

15

1600

200

140