Item |
Test Items |
Standard requirements |
Test Results |
Conclusion |
|
Prefabricated (cold-shrinkable) outdoor terminal/intermediate joint for 27.5kV electrified railway |
Power frequency withstand voltage test |
124kV, 5min no flashover, no breakdown |
124kV, 5min, no breakdown or flashover of the combined sample |
Pass |
|
Power frequency withstand voltage test under rain |
110kV, 1min no flashover, no breakdown |
110kV, 1min, no breakdown or flashover of the combined sample |
Pass |
|
|
Partial discharge test at room temperature |
48kV discharged power is not more than 5pc |
The discharge capacity of each phase of the combined sample at 48kV is not more than 1.7pc. |
Pass |
|
|
Impulse voltage test at high temperature |
± 250kV 10 times each without breakdown or flashover |
± 250KV 10 times each. No breakdown or flashover of each phase of the combined sample |
Pass |
|
|
Constant pressure load cycle test in air |
69kV voltage and conductor heating to temperature 90-100 ℃. A total of 60 cycles without breakdown and flashover |
69kV voltage and conductor temperature 90-100 ℃, a total of 60 cycles, the combination of samples are not broken down, not flashover |
Pass |