24kV Cold Shrink Cable Terminations and Mid-Joints
Negotiable
China
No. 6, Minxin East Road, Lvdao Industrial Zone, Luquan District, Shijiazhuang City
+86311-82232877
Online Contact
Favorite
Product Introduction

Table 1:

Model

Name

Applicable cable cross-sectional area (mm²)

HLW(N.J)-24-□/1

HLW(NJ)-24-□/2

HLW(NJ)-24-□/3

HLW(NJ)-24-□/4

HLW(N.J)-24-□/5

HLW(NJ)-24-□/6

HLW(NJ)-24-□/7

24kV Silicone Rubber Cold Shrinkable Outdoor Collateral End

25-50

70-120

150-240

300-400

500-630

800-1200

Table 2:

Project

Test Items

Standard requirements

Test Results

Conclusion

24KV Silicone Rubber Cold Shrinkable Indoor/External Terminal Head/Intermediate Head

1min power frequency withstand voltage test

55kV, 1min no flashover, no breakdown

55kV, 1min, each phase of the combined sample is not flashover, not breakdown

Pass

Partial discharge test

18kV discharged power ≤ 5pc

18kV discharged power ≤ 5pc

Pass

Load cycle test

The conductor is heated to 95 ℃, each cycle is 8h, of which heating is 5h and cooling is 3h, a total of three cycles

Complete three load cycle tests as per standard requirements

Evaluated by the following tests

Partial discharge test

18kV discharged power ≤ 5pc

18kV discharged power ≤ 5pc

Pass

Lightning impulse voltage test

± 125kV, positive and negative polarities 10 times respectively, no breakdown, no flashover

± 125kV 10 times each, each phase of the combined sample has no flashover and no breakdown

Pass

Negative polarity 15min DC withstand voltage test

72kV, 15min no flashover, no breakdown

72kV, 15min, each phase of the combined sample has no flashover and no breakdown

Pass

4h power frequency withstand voltage test

48kV, 4h no flashover, no breakdown

48KV, 4h, each phase of the combined sample has no flashover and no breakdown.

Pass