Table 1:
|
Conductor cross-sectional area (mm²) |
Design serial number |
|
25-50 |
1 |
|
70-120 |
2 |
|
150-240 |
3 |
|
300-400 |
4 |
|
500 |
5 |
|
630 |
6 |
|
800 |
7 |
|
1000 |
8 |
|
1200 |
9 |
|
1400 |
10 |
|
1600 |
11 |
|
1800 |
12 |
|
2000 |
13 |
Table 2:
|
Project |
Test Items |
Standard requirements |
Test Results |
Conclusion |
|
8.7/15kV Silicone Rubber Cold Shrinkable Indoor/External Terminal/Intermediate Terminal |
1min power frequency withstand voltage test |
45kV, 1min no flashover, no breakdown |
45kV, 1min, each phase of the combined sample has no flashover and no breakdown |
Pass |
|
Partial discharge test |
13kv decentralized power ≤ 5pc |
13kV discharged power ≤ 5pc |
Pass |
|
|
Load cycle test |
The conductor is heated to 90°C -95°C for 8h per cycle. Heating for 5h and cooling for 3h, three cycles in total |
Complete three load cycle tests as per standard requirements |
Evaluated by the following tests |
|
|
Partial discharge test |
13kV discharged power ≤ 5pc |
13kV discharged power ≤ 5pc |
Pass |
|
|
Lightning impulse voltage test |
± 105KV 10 times each, no flashover, no breakdown |
± 105KV 10 times each, each phase of the combined sample has no flashover and no breakdown |
Pass |
|
|
Negative polarity 15min DC withstand voltage test |
52kV, 15min no flashover, no breakdown |
52kV, 15min, each phase of the combined sample has no flashover and no breakdown |
Pass |
|
|
4h power frequency withstand voltage test |
35kV, 4h without flashover and breakdown |
35kV, 4h, each phase of the combined sample has no flashover and no breakdown |
Pass |