JP Low-voltage Integrated Distribution Box
Negotiable
China
No.12 Hongtai Road, Huaming Street, Dongli District, Tianjin City
15822469629
Online Contact
Favorite
Product Parameters

Product Configuration

Product Parameters

Transformer capacity (kVA)

50

100

200

400

Rated operating voltage (V)

400

Rated frequency (Hz)

50

Rated insulation voltage (V)

690

Incoming fuse-type disconnecting switch

Rated current (A)

630(400/200)

Rated insulation voltage (V)

1000

Number of poles

3P

Fuse limit segmentation capacity (kA)

≥ 30

Appearance of residual current operating current protector

Leakage action current (mA)

Leakage action current is 30~500 (adjustable)

Rated current (A)

630+2 x 400(400+250)

Rated operating short-circuit breaking capacity(kV)

≥ 35

Type of release

Electronic, with RS485 communication function

Number of poles

3P+N

Outlet circuit number

1 to 3

Lightning protection and grounding part

The main circuit adopts T1 surge protector, and the compensation circuit adopts metal zinc oxide.Arrester

Busbar/Pile Head Temperature Measurement

Induction power, wireless transmission

Power quality control device

120kvar(30kvar active power module +90kvar passive power module)

Emergency power interface

The emergency power interface is reserved after the incoming switch, and the fast connection system technology is adopted, Provide fast, safe and efficient connection of emergency power

Box material

304 stainless steel or SMC (spray ral7035)

Dimensions: width x depth x height (mm)

1350 × 700 × 1200(800 × 650 × 1200)

Protection level

≥ IP44