Product Introduction

The FTU is a monitoring and protection device specifically developed for pole-mounted switches in 10kV distribution networks. It features fault detection, protection control, and communication functions (when equipped with a communication module). It is designed to be used with switches installed at the responsibility demarcation point of customer incoming lines on 10kV overhead distribution lines, as well as on main feeder lines requiring reliable segmentation.

When combined with a pole-mounted switch and voltage transformers, the FTU forms a complete system capable of automatically isolating single-phase-to-ground faults on the controlled branch and automatically isolating phase-to-phase short-circuit faults on the controlled branch.

Key Features

Advanced Fault Detection: Rapidly detects various types of faults

Effective Protection & Control: Ensures safety and stability of the power grid

Reliable Communication: Enables efficient data transmission

Versatile Application: Suitable for different installation locations

High Accuracy: Provides precise detection and control

Product Parameters

Technical parameters

Project

Unit

Parameters

Input operating voltage

V

AC220(*)

Input operating voltage frequency

Hz

50

Allowable fluctuation range of input operating voltage

%

± 15

Power consumption of the whole machine

<20VA

Rated voltage of switching quantity

V

DC24

Output voltage (closing/opening operation)

V

DC24 (*)

Phase current sampling input range

0 ~ 12A (secondary value)

Zero sequence current sampling input range

a.Direct sampling (0-6A)

b.Self-produced (0-10A) and are all secondary values

Phase current sampling error

%

± 0.5

Zero sequence current sampling error

a.Direct sampling (± 0.2%)

b.Self-produced (± 0.5%)

Zero sequence voltage sampling rating

2.17V (electronic transformer)

Fixed value of phase-to-phase short circuit overcurrent protection

0.5 ~ 10A (step 0.01A)

Interphase short circuit overcurrent protection action time

0~99S (step 0.01S)

Fixed value of single-phase grounding protection current

a.Direct sampling (0.01In ~ 0.95In)

b.self-produced (0.01In ~ 12In) step size is 0.01A

Fixed value of single-phase grounding protection time

0~7200S (step 0.01S)

Remote control distance

≤50m

* Other working voltages need to be specified in advance

Applicable environment

Temperature: -40 ~ +85; outdoor, no flammable, explosive hazard, chemical corrosion of the place