Product Overview
As a key component of the security and stability control system, the PCS-992 series power system security and stability control device adopts a distributed architecture consisting of one master station and multiple slave stations interconnected via optical fiber. Slave stations handle sampling, calculation, fault detection, and local tripping for their respective units. The master station collects operating status and fault judgment results from all slave stations, exchanges information and commands with stability control devices at other stations via communication interface units, identifies system operating mode, detects grid faults, calculates stability control measures or control targets based on the local stability control strategy, and then issues commands to slave stations or transmits them to stability control devices at other stations for execution.
Product Functions
Control Functions
Emergency control following AC grid faults
Emergency control following HVDC/UHVDC faults
Overload control
Integrated source-grid-load-storage control
Reactive power and voltage emergency control
Low-frequency/low-voltage load shedding and islanding
High-frequency generator tripping and islanding
Enterprise grid security and stability control
AC tie-line power loss monitoring / last breaker protection
Photovoltaic anti-islanding protection
Precise load-shedding control
Auxiliary Functions
Online hardware and loop monitoring
Minute pulse, second pulse, and IRIG-B time synchronization
128 event reports, 32 fault recording reports (master records phasors, slaves record instantaneous values)
Diverse communication solutions supporting power industry standards IEC 60870-5-103 and IEC 61850
User-friendly HMI with convenient supporting debugging software and powerful waveform analysis tools
Practical and portable dynamic full-system simulation test platform for power systems