Rated HV 33、35、36、37、38.5KV Tapping range ±2×2.5 Connection Symbol Dyn11或Yyn0
Rated LV 0.4KV Insulation grade Class F or Class H Insulation Level LI170AC70/AC3
Model No-load Loss
Po kW
Load Loss (Class F) Pk
(120℃)KW
Load Loss (Class H) Pk
(145℃)KW
Impedance Voltage
Uk%
No-load current lo% Noise
LpAdB
Total Weight KG Dimensions L×W×H Center Distance
Body (mm) Shell (mm) A×B(mm)
SC11-50/35 0.41  1.42  1.52  2.3  50  530  1360×720×1200 2000  1500  1900  660×720
SC11-100/35 0.57  2.09  2.23  50  690  1410×720×1250 2000  1500  1900  660×720
SC11-160/35 0.72  2.81  1.5  50  900  1450×720×1280 2000  1500  1900  660×720
SC11-200/35 0.79  3.32  3.55  1.5  50  1000  1490×720×1300 2000  1500  1900  660×720
SC11-250/35 0.89  3.8  4.06  1.3  50  1190  1520×720×1360 2000  1500  1900  660×720
SCB11-315/35 1.05  4.51  4.82  1.3  50  1400  1550×880×1420 2200  1600  2200  820×820
SCB11-400/35 1.25  5.41  5.79  1.1  50  2110  1590×880×1450 2200  1600  2200  820×820
SCB11-500/35 1.46  6.65  7.11  1.1  50  2390  1620×880×1500 2200  1600  2200  820×820
SCB11-630/35 1.67  7.69  8.28  52  2800  1620×880×1550 2200  1600  2200  820×820
SCB11-800/35 1.95  9.12  9.76  52  3280  1700×1130×1590 2300  1700  2400  820×1070
SCB11-1000/35 2.19  10.4  11.1  0.75  52  3730  1700×1130×1690 2300  1700  2400  1070×1070
SCB11-1250/35 2.55  12.7  13.6  0.75  54  4330  1770×1130×1815 2500  1800  2600  1070×1070
SCB11-1600/35 2.92  15.4  16.5  0.75  54  5100  1840×1130×1905 2500  1800  2600  1070×1070
SCB11-2000/35 3.44  18.2  19.5  0.75  54  5940  1900×1230×2020 2700  1900  2800  1070×1170
SCB11-2500/35 4.01  21.8  23.3  0.75  54  6500  1950×1230×2020 2700  1900  2800  1070×1170

Note: The size data in the items marked with "*" is subject to change without prior notice, and the final sizes are subject to the final assembly drawing provided.