Service Conditions:
Installation Location: Indoor or outdoor;
Ambient Air Temperature: -30℃~+40℃ (special order -50℃~+50 ℃);
Air Humidity: Relative humidity: daily average not greater than 95%;
Monthly average not greater than 90%;
Saturated vapor pressure: daily average not greater than 2.2 kPa;
Monthly average not greater than 1.8 kPa;
Altitude not exceeding 1000 m (special order unlimited);
Solar radiation intensity 1000 W/m² (0.5 m/s wind speed);
Pollution level IV;
Wind speed not exceeding 34 m/s (corresponding to 700 Pa on cylindrical surface);
Ice coating level 10;
Seismic fortification intensity 9 degrees, horizontal acceleration ≤0.5 g, vertical acceleration ≤0.25 g;