ZW32-12/630-20 Outdoor High Voltage AC Vacuum Circuit Breaker

Negotiable
China
No.6 Xianghai Road, Xiamen Torch High-tech Zone (Xiang'an) Industrial Park
+86 592 3671600
Online Contact
Favorite
Product Introduction

The ZW32-12 series outdoor AC high voltage vacuum circuit breaker (pole-mounted switch) is a three-phase AC 50Hz outdoor high voltage switchgear, mainly used in 10kV outdoor distribution systems of rural or urban networks, for breaking and closing load current, overload current, and short-circuit current, and also for other similar places.

Service Conditions

Normal Service Conditions

  • Altitude: not exceeding 2000m;
  • Ambient air temperature: -40℃~+40℃
  • Ambient air may be polluted by dust, smoke, corrosive gas, steam or

salt fog;

  • Wind speed not exceeding 35m/s;
  • No frequent severe vibration places;
  • Pollution level: III.

Special Service Conditions

  • The circuit breaker can be used under normal service conditions different from the above. In this case, the user's requirements should be negotiated with the manufacturer and a consistent opinion obtained.

 

Product Parameters

Main Technical Parameters of the Circuit Breaker

Name Unit Value
Rated Voltage kV 12 
Rated 1min Power Frequency Withstand Voltage kV 42 
Lightning Impulse Withstand Voltage kV 75 
Rated Frequency Hz 50 
Rated Current A 630 
Rated Short-circuit Breaking Current kA 12.5  16  20 
Rated Short-circuit Making Current (peak) kA 31.5  40  50 
Rated Peak Withstand Current kA 31.5  40  50 
Rated Short-time Withstand Current kA 12.5  16  20 
Rated Short-circuit Duration S
Number of Rated Short-circuit Breaking Current Operations Times 30 
Rated Operating Sequence   O-0.3s-CO-180-CO
Mechanical Life Times 10000 
Overcurrent Trip Current A
1min Power Frequency Withstand Voltage of Secondary Circuit V 2000 

Circuit Breaker Parameters

Name Configuration Unit Value
Contact Travel mm 3±0.5
Contact Gap mm 9±1
Average Closing Speed m/s 0.8±0.2
Average Opening Speed m/s 1.4±0.2
Contact Closing Bounce Time ms ≤2
Three-phase Contact Closing Asynchrony ms ≤2
Three-phase Contact Opening Asynchrony ms ≤2
Resistance of Main Circuit per Phase Without Disconnecting Switch   <80
With Disconnecting Switch   <150
Pole Center Distance mm 280~340

Main Technical Parameters of CTB Spring Operating Mechanism

No. Name Rated Voltage Normal Operating Range
Opening Coil DC110 Reliable tripping under DC65% or AC85%-120% rated voltage;
no tripping under less than 30% rated voltage
DC220
AC220
Closing Coil DC110 Reliable tripping under DC80% or AC85%~110% rated voltage
DC220
AC220
Energy Storage Motor Rated Voltage: DC/AC 220V  
Rated Power: 40W
Closing Spring Energy Storage Time ≤8s Reliable operation under 85%-110% rated voltage

Disconnecting Switch Parameters

Name Unit Value
Rated Voltage kV 12 
Rated 1min Power Frequency Withstand Voltage kV 42 
Lightning Impulse Withstand Voltage kV 75 
4s Rated Short-time Withstand Current kA 20 
Manual Operating Torque N.m ≤200
Contact Just-closed Position Offset mm
Isolation Contact Gap mm ≥200
Insulation Distance of Conductive Part to Ground mm ≥200