VDS-12/40.5 Series Vacuum Circuit Breaker

Negotiable
China
No.868 Jiahang Road, Jiading District, Shanghai
+86 21 69900817
Online Contact
Favorite
Product Introduction

The VDS-12/40.5 series vacuum circuit breaker is a new type of circuit breaker independently developed by Shanghai Pinggao Tianling Switchgear Co., Ltd. This product is suitable for indoor switchgear with rated voltage 12kV-40.5kV and three-phase AC 50Hz, serving as a control and protection unit for high-voltage electrical equipment. It is widely used in power plants, power grids, petrochemical, metallurgy, coal mines, and urban infrastructure construction projects such as subways, airports, and buildings. The circuit breaker adopts a modular spring operating mechanism, which is simple and mature with reliable and convenient operation. It can perform frequent operations or multiple short-circuit current interruptions within the working current range. The VDS series vacuum circuit breaker can be used alone or in N2X-12/24 and N2S/N2N-40.5 series gas insulated metal-enclosed switchgear, and can be interchanged with similar foreign products.

Product Parameters

VDS-12 Vacuum Circuit Breaker Technical Parameters

Item

Unit

Parameter

Rated Voltage

kV

12

Rated Insulation Level

Short-Time Power Frequency Withstand Voltage / Open Contacts

To Earth and Between Phases: 42; Open Contacts: 48

Lightning Impulse Withstand Voltage

To Earth and Between Phases: 75; Open Contacts: 85

Rated Frequency

Hz

50

Rated Current

A

630、1250、2000、2500、3150

3150、4000

Rated Short-Circuit Breaking Current

kA

20

25

31.5

40

Rated Short-Time Withstand Current

20

25

31.5

40

Rated Short-Circuit Making Current (Peak)

50

63

80

100

Rated Peak Withstand Current

50

63

80

100

Rated Phase-to-Phase Short-Circuit Breaking Current

27.4

Rated Out-of-Step Breaking Current

/

Rated Out-of-Step Making Current

/

Rated Short-Circuit Duration

s

4

Rated Single / Back-to-Back Capacitor Bank Switching Current

A

630/400

VDS-40.5 Vacuum Circuit Breaker Technical Parameters

Item

Unit

Parameter

Rated Voltage

kV

40.5

Rated Frequency

Hz

50/60

Rated Current

A

1250

2500

Rated Short-Time Power Frequency

Between Phases and to Earth

 

95

Withstand Voltage (1min, RMS)

Open Contacts

kV

118

Auxiliary and Control Circuits

2

Rated Lightning Impulse
Withstand Voltage (Peak)

Between Phases and to Earth

kV

185

Open Contacts

215

Rated Short-Time Withstand Current

kA

25/31.5

Partial Discharge Level

pC

≤10

Rated Peak Withstand Current

kA

63/80

Rated Short-Circuit Duration

s

4

Rated Short-Circuit Breaking Current

kA

25/31.5

Rated Short-Circuit Making Current

kA

63/80

Rated Operation Sequence

 

O-0.3s-CO-180s-CO

Rated Short-Circuit Breaking Current Operations

Times

30(E2)

Rated Phase-to-Phase Earth Fault Breaking Current

kA

21.8/27.4

Rated Out-of-Step Breaking Current

kA

6.3/7.9

Rated Cable Charging Breaking Current

A

50(C2)

Rated Operating Voltage of Operating Circuit

V

DC/AC220

Rated Supply Voltage of Energy Storage Motor

V

DC/AC220

Energy Storage Time

s

≤15

Closing/Opening Trip Coil Working Current

A

1.3

Energy Storage Motor Power

W

120

Main Circuit Resistance

μΩ

≤60

≤45

Mechanical Operations

Times

10000(M2)