LCG-12 Environmentally Friendly Gas Insulated Metal-Enclosed Switchgear

Negotiable
China
No.868 Jiahang Road, Jiading District, Shanghai
+86 21 69900817
Online Contact
Favorite
Product Introduction

Product Features:

·Micro-positive pressure nitrogen or dry air insulation, vacuum interruption; insulation characteristics are unaffected by altitude, moisture, or pollution.

·Modular structure design. The main switch adopts three-position switch-vacuum load switch or three-position switch-vacuum circuit breaker structure.

·Line-side grounding is realized by closing the vacuum arc-extinguishing chamber, with no risk of insulation gas degradation and longer electrical life.

·Rated filling pressure 0.02MPa (relative value, 20°C) gauge pressure. All electrical performance is met at zero gauge pressure under normal conditions.

·Compact structure, flexible solutions, convenient combination, small footprint, and no gas handling required on site.

·Laser welding and helium leak detection ensure the air tightness and long-term weather resistance of the gas tank.

·Silicone rubber plug-in connection structure is adopted to realize plug-in installation of high-voltage components and expansion of the cabinet.

·Can be equipped with intelligent remote control, monitoring units, and integrated digital relays.

Product Parameters

Item

Unit

Load Switch Cabinet

Circuit Breaker Cabinet

Rated Voltage

kV

12

12

Rated Current

A

630

630

Rated Frequency

Hz

50

50

Rated Short-Time Power Frequency Withstand Voltage (RMS)

To Earth and Between Phases

kV

42

42

Across Isolating Distance

48

48

Rated Lightning Impulse Withstand Voltage (Peak)

To Earth and Between Phases

kV

75

75

Across Isolating Distance

85

85

Rated Short-Circuit Breaking Current

kA

-

20/25

Rated Short-Circuit Making Current (Peak)

kA

50/63

50/63

Rated Short-Time Withstand Current/Time

kA/s

20/4;25/4

20/4;25/4

Rated Peak Withstand Current

kA

50/63

50/63

Rated Active Load Breaking Current

A

630

-

Rated Active Load Breaking Operations

Times

200

-

Rated Loop Breaking Current

A

630

-

Rated Cable Charging Breaking Current

A

50

50

Mechanical Life

Three-Position Switch

Times

3000

3000

Vacuum Circuit Breaker

Times

-

10000

Vacuum Load Switch

Times

10000

 

Short-Circuit Breaking Electrical Life Class

   

E2

Rated Operation Sequence

   

O-0.3s-CO-3min-CO

Insulating Gas

 

Nitrogen/Dry Air

Nitrogen/Dry Air

Rated Filling Pressure (rel. 20°C)

MPa

0.02

0.02

Minimum Working Pressure (rel. 20°C)

MPa

0

0

Annual Leakage Rate

%/Y

≤0.05

≤0.05

Protection Degree

High-Voltage Components

 

IP67

IP67

Low-Voltage Components

 

IP4X

IP4X

Rated Auxiliary Circuit Voltage

V

DC24,48,110,220 AC220

DC24,48,110,220 AC220

Cabinet Dimensions (Width x Depth x Height)

mm

375x750x1450

440x750x1450/420x950x(1650+350)