Product specifications table
|
|
|
Model (capacity KVA)
|
SMP(5K 10K 15K 20K 30K 40K 50K)
|
SMP(60K 80K)
|
|
|
UPS type
|
Double isolation, double conversion online
|
|
Efficiency
|
> 93%
|
|
UPS ambient temperature
|
-30~40 ℃(+55 ℃, full load operation time 16h)
|
|
UPS storage temperature
|
-30 ~ +70 ℃
|
|
Relative humidity
|
<95% (non-condensation)
|
|
Altitude
|
<1500m
|
|
Power reduction at height> 1500m
|
7%/km
|
|
Ventilation mode
|
1+1 redundant fan, forced air cooling, up and down air supply
|
|
Noise
|
<60dBA
|
|
Input/output cable connection
|
Bottom or Top
|
|
Communication interface
|
RS232(1)/RS485(1)/dry contact (1 group),SSMP optional
|
|
Specification
|
CE, EN50091-1,2
|
Compliant
|
|
FCC CLASS A
|
Compliant
|
|
Protection circuit
|
Short circuit protection
|
Rectifier/Standby Power Supply/Bypass Switch
|
|
Lightning protection
|
MOV
|
|
EMC filtering
|
Input & Output
|
|
Isolation
|
Input/output full isolation
|
|
Rectifier
|
|
Bridge rectifier
|
Three-phase 6-pulse controlled rectifier
|
Three-phase 12-pulse controlled rectifier
|
|
Rated input voltage (VAC)
|
380V-25% + 30%, three-phase three-wire or three-phase four-wire
|
|
Input frequency
|
50/60Hz ± 10%
|
|
Input power factor
|
> 0.75
|
> 0.85
|
|
DC output voltage
|
110VDC/220VDC
|
|
DC output voltage accuracy (load 0~100% change)
|
± 1%
|
|
Efficiency
|
> 0.85
|
> 0.9
|
|
Inverter
|
|
Bridge inverter
|
IGBT DSP controlled inverter IGBT
|
|
DC input range
|
110VDC/220VDC ± 25%
|
|
Rated output voltage
|
110V/220/230VAC,2P2W or 120V/240VAC,2P2W
|
|
Output power factor
|
0.8
|
|
Output frequency
|
50/60Hz ± 0.1%
|
|
Output voltage stability
|
Static
|
± 1%
|
|
Dynamic (0~100%~ 0)
|
± 5%
|
|
Output voltage recovery time
|
Recovery to 2% in 10 ms after step load
|
|
Overload capacity
|
125% for 10min,150% for 1min
|
|
Short circuit characteristics
|
Short circuit protection, current limited to 3 times the rated current, 100ms
|
|
Output waveform
|
Sine wave
|
|
Output wave distortion
|
Linear load
|
<1%
|
|
Non-linear load (crest factor 3:1)
|
<2%
|
|
Peak factor
|
3:1 (customizable> 3:1 crest factor)
|
|
Efficiency
|
> 94%
|
|
DC cold start
|
Yes
|
|
Bypass
|
|
Automatic static switch
|
Thyristor SCR
|
|
Rated voltage
|
110V/220V/230V ± 20% (settable) or 120V/240V ± 20% (settable)
|
|
Rated frequency
|
50/60Hz ± 5% (settable)
|
|
Static bypass transition time
|
<0.4ms
|
|
Inverter to static bypass
|
Test inverter, inverter fault, inverter input voltage excess, inverter output voltage excess
|
|
Overload capacity
|
100-110%
|
Long-term operation
|
|
> 110-125%
|
10min
|
|
> 125-150%
|
1min
|
|
> 150 percent
|
100ms
|
|
Mechanical specifications
|
|
Model
|
SMP5K 10K 15k 20K 30k
|
SMP40k 50k
|
SMP60K 80k
|
|
Protection level
|
IP20,IP21,IP30,IP32,IP40,IP42 optional, others can be customized
|
|
Cabinet size
|
W
|
600
|
800
|
1200
|
|
D
|
800
|
|
H₁
|
1800(IP20, IP30, IP40)
|
|
H₂
|
2000(IP21, IP32, IP42)
|
|
Weight (kg)
|
700~800
|
800~1000
|
1100~2000
|