The DBW series compensating voltage regulator (AVR) is a new generation power regulator developed by our company, utilizing U.S. technology and tailored to the actual voltage conditions of domestic power grids. This regulator automatically maintains stable output voltage when external power grid voltage fluctuates or when load changes.

Key advantages include large capacity, wide range, low loss (energy-saving type), high accuracy, fast voltage adjustment speed, and no waveform distortion.

It offers smooth voltage regulation, can handle instantaneous overloads, and is suitable for various linear and nonlinear loads.

The user-friendly Chinese LCD display facilitates ease of use and maintenance.

The power devices within the DBW series compensating AC voltage regulator cabinet utilize forced air cooling, with air intake from the bottom and exhaust from the top, employing axial flow AC fans that have a continuous operating life of no less than 50,000 hours (GB/T2658). The cooling air flow for each 40 kVA output capacity regulator cabinet is no less than 15 m³/min.

Product Parameters

Product specifications table

Electrical performance specifications of the whole machine

Rated input voltage level

400VAC/230VAC/120VAC

Input voltage range

400VAC ± 20%/230VAC ± 20%/120VAC ± 20%

Input frequency range

50Hz ± 10%/60Hz ± 10%

Rated output voltage

380VAC ± 5%/220VAC ± 5%/110VAC ± 5%

Voltage stabilization accuracy

≤ ± 5%

Output with load capacity

110% rated load, long-term operation; 120% rated load, 60 Minutes operation;140% rated load for 15 minutes; 160% rated load for 5 minutes;

Efficiency

At rated load, ≥ 95%;

Three-phase voltage asymmetry

For three-phase output, (asymmetry of output voltage-asymmetry of input voltage) ≤ ± 1%;

Asymmetry of voltage = (negative sequence component/Positive sequence component) × 100%

output voltage waveform relative harmonic content

(Output voltage waveform harmonic content-input voltage waveform harmonic content) ≤ ± 10%

Stabilization time

When the input voltage step is 10% of the rated voltage, the adjustment time shall be less than or equal to 1.5 seconds.

Insulation

Between winding and shell and between winding, 3KV test, insulation resistance ≥ 1MΩ

Compressive strength

2000V, 1 minute

Electrical clearance and creepage distance

Electrical clearance ≥ 6mm; Creepage distance ≥ 10mm;

Noise

≤ 65db

Temperature rise

After the thermal equilibrium of the whole machine, the limit temperature rise of the winding or coil in the machine is ≤ 80 ℃; The limit temperature rise at the contact of the brush is ≤ 120 ℃;

Brush life

≥ 10000 adjustments

Protection function

It is equipped with output overvoltage protection, output undervoltage protection, output overcurrent protection, output short circuit protection and voltage regulating motor stroke protection;With output overvoltage protection, output undervoltage protection, output overcurrent protection, output short circuit protection action, sound, light, electricity alarm, and cut off the output.

Single-in single-out isolation transformer specifications

Rated input voltage

400VAC/230VAC

Input voltage range

320V-480V/185V-275V

Input frequency range

50Hz ± 10%/60Hz ± 10%

Heat resistance class of insulation

Class B

Insulation

Between winding and shell and between winding, 3KV test, insulation resistance ≥ 1MQ

No-load loss

40KVA and below, ≤ 3% rated capacity; 50KVA and above, ≤ 2% rated capacity;

Short circuit loss

40KVA and below, ≤ 3% rated capacity; 50KVA and above, ≤ 2% rated capacity;

Three-in single/three-out isolation transformer specifications

Rated input line voltage

400VAC

Input voltage range

320V-480V

Input frequency range

50Hz ± 10%/60Hz ± 10%

Heat resistance class of insulation

Class B

Insulation

Between winding and shell and between winding, 3KV test, insulation resistance ≥ 1MΩ

No-load loss

40KVA and below, ≤ 5% rated capacity; 50KVA and above, ≤ 4% rated capacity;

Short circuit loss

40KVA and below, ≤ 5% rated capacity; 50KVA and above, ≤ 4% rated capacity;

Specifications of compensation transformer

Rated input voltage

210VAC/105VAC

Input voltage range

0V-210V/0V-105V

Input frequency range

50Hz ± 10%/60Hz ± 10%

Heat resistance class of insulation

Class B

Insulation

Between winding and shell and between winding, 3KV test, insulation resistance ≥ 1MQ

No-load loss

≤ 2% of rated capacity;

Short circuit loss

≤ 2% of rated capacity;

Voltage regulator specifications

Rated input voltage

220VAC/110VAC

Input voltage range

220V ± 5%/110V ± 5%

Input frequency range

50Hz ± 10%/60Hz ± 10%

Output voltage range

0V ~ 210V/0V ~ 105V

Heat resistance class of insulation

Class B

Insulation

Between winding and shell and between winding, 3KV test, insulation resistance ≥ 1MQ

No-load loss

≤ 2% of rated capacity;

Short circuit loss

≤ 2% of rated capacity;

Full motor adjustment time

≤ 4 seconds

Mechanical specifications

Model

DBW/SBW10

DBW/SBW15

DBW/SBW20

DBW/SBW30

DBW/SBW40

DBW/SBW60

DBW/SBW80

DBW/SBW100

DBW/SBW120

DBW/SBW160

DBW/SBW200

Protection level

IP20,IP21,IP30,IP32,IP40,IP42 optional

Size of gauge body (mm)

W(D)

600

1200

1800

W(S)

600

1200

1800

D

800

H₁

1800(IP20, IP30, IP40)

H₂

2000(IP21, IP32, IP42)

Weight (kg)

700

730

750

850

1000

1200

1500

1800

2000

2500