Rated capacity (kVA) |
Voltage combination and tap range |
Bonding Group Label |
Level 1 Energy Efficiency |
Level 2 Energy Efficiency |
Level 3 Energy Efficiency |
Short circuit impedance (%) |
|||||
|
High voltage (kV) |
High voltage tap range (%) |
Low voltage (kV) |
No-load loss (kW) |
Load loss (kW) |
No-load loss (kW) |
Load loss (kW) |
No-load loss (kW) |
Load loss (kW) |
|||
|
2000 |
35 |
± 3 × 2.5 |
6.3 10.5 |
Yd11 |
1.28 |
15.79 |
1.49 |
15.79 |
1.85 |
16.72 |
6.5 |
|
2500 |
1.51 |
18.67 |
1.77 |
18.67 |
2.19 |
19.76 |
|||||
|
3150 |
35 to 38.5 |
± 3 × 2.5 |
6.3 10.5 |
1.8 |
22.2 |
2.1 |
22.2 |
2.6 |
23.5 |
7.0 |
|
|
4000 |
2.1 |
26.2 |
2.5 |
26.2 |
3.1 |
27.6 |
|||||
|
5000 |
2.6 |
30.8 |
3.0 |
30.8 |
3.7 |
32.5 |
|||||
|
6300 |
3.1 |
33.0 |
3.7 |
33.0 |
4.5 |
34.9 |
8.0 |
||||
|
8000 |
35 to 38.5 |
± 3 × 2.5 |
6.3 6.6 10.5 |
YNd11 |
4.3 |
36.5 |
5.1 |
36.5 |
6.3 |
38.6 |
|
|
10000 |
5.1 |
43.2 |
6.0 |
43.2 |
7.4 |
45.6 |
|||||
|
12500 |
6.0 |
51.1 |
7.1 |
51.1 |
8.7 |
54.0 |
|||||
|
16000 |
7.2 |
63.3 |
8.5 |
63.3 |
10.5 |
66.8 |
|||||
|
20000 |
8.5 |
74.4 |
10.1 |
74.4 |
12.4 |
78.6 |
|||||
|
25000 |
10.1 |
88.0 |
11.9 |
88.0 |
14.6 |
92.9 |
10.0 |
||||
|
31500 |
12.0 |
104.4 |
14.2 |
104.4 |
17.4 |
110.2 |
|||||
|
Note: 1. For transformers with low voltage of 10.5kV, products with connection group label Dyn11 can be provided; 2. Transformers with various special parameters and performance can be manufactured according to user requirements. |
|||||||||||