Rated capacity (kVA) |
Voltage combination and tap range |
Bonding Group Label |
Level 1 Energy Efficiency |
Level 2 Energy Efficiency |
Level 3 Energy Efficiency |
Short circuit impedance (%) |
||||||
|
High voltage and tap range (kV) |
Medium voltage (kV) |
Low voltage (kV) |
No-load loss (kW) |
Load loss (kW) |
No-load loss (kW) |
Load loss (kW) |
No-load loss (kW) |
Load loss (kW) |
Step-up |
Step-down |
||
|
31500 |
220±2 × 2.5% 230±2 × 2.5% 242±2 × 2.5% |
69 115 121 |
6.3 6.6 10.521 36 37 38.5 |
YNyn0d11 |
18 |
138 |
21 |
138 |
26 |
145 |
High-Medium 22~24 High-Low 12~14 Medium-Low 7~9 |
High-Medium 12~14 High-Low 22-24 Medium-Low 7 to 9 |
|
40000 |
21 |
165 |
25 |
165 |
30 |
174 |
||||||
|
50000 |
24 |
194 |
29 |
194 |
35 |
205 |
||||||
|
63000 |
29 |
231 |
34 |
231 |
42 |
244 |
||||||
|
90000 |
10.513.821 36 37 38.5 |
37 |
300 |
44 |
300 |
54 |
316 |
|||||
|
120000 |
46 |
369 |
55 |
369 |
67 |
390 |
||||||
|
150000 |
10.5 13.8 15.75 21 36 37 38.5 |
55 |
438 |
65 |
438 |
80 |
463 |
|||||
|
180000 |
62 |
500 |
73 |
500 |
90 |
527 |
||||||
|
240000 |
72 |
616 |
91 |
616 |
112 |
650 |
||||||
|
300000 |
91 |
726 |
108 |
726 |
133 |
767 |
||||||
|
Note: 1. The capacity allocation of load loss in the table is (100/100/100%, and the capacity allocation of boost structure is (100/50/100)%; The capacity allocation of buck structure can be (100/100/50% or (100/100)%; 2. Transformers with various special parameters and performance can be manufactured according to user requirements. |
||||||||||||