Application:
The cable is used in power transmission and distribution systems with rated voltages of 0.6/1, 1.8/3, 3.6/6, 6/6, 6/10, 8.7/10, 8.7/15, 12/20, 18/20, 18/30, 21/35, 26/35kV.
Model and Name
| Model | Name |
|---|---|
| YJV YJLV |
Copper or aluminum core cross-linked polyethylene insulated, polyvinyl chloride sheathed power cable |
| YJV22 YJLV22 |
Copper or aluminum core cross-linked polyethylene insulated, steel tape armored, polyvinyl chloride sheathed power cable |
| YJV32、YJV42 YJLV32、YJLV42 |
Copper or aluminum core cross-linked polyethylene insulated, steel wire armored, polyvinyl chloride sheathed power cable |
Cable Installation and Operating Conditions
Cable Installation
-
1. Cable temperature during installation shall not be lower than 0°C. When ambient temperature is below 0°C, the cable should be preheated;
-
2. Bending radius during installation shall not be less than 12 times the cable outer diameter;
-
3. After installation, apply 4U0 DC voltage for 15 minutes for cables 3kV and below; apply phase-to-phase voltage U AC voltage for 15 minutes for cables 6kV and above.
Installation in Air
-
1. When single-core cables are laid in parallel, center distance is 2 times cable diameter for 185mm2 and below, and 90mm for 240mm2 and above;
-
2. Ambient temperature: 40°C;
-
3. Maximum allowable conductor temperature: 90°C;
-
4. Ampacity correction factor at different ambient temperatures:
|
Ambient Temperature |
20°C |
25°C |
35°C |
40°C |
|---|---|---|---|---|
|
Correction Factor |
1.23 |
1.17 |
1.06 |
1.0 |
Direct Burial Installation
-
1. When single-core cables are laid without contact, center distance is 2 times cable diameter;
-
2. Ambient temperature 20°C;
-
3. Maximum allowable conductor temperature: 70°C;
-
4. Soil thermal resistivity: 1.0°C·m/W;
-
5. Burial depth: 0.7m;
- 6. Ampacity correction factor at different ambient temperatures;