Medium-voltage spring-operated circuit breaker for distribution systems up to 40.5 kV, 2500 A, 31.5 kA
The OVB-VBF outdoor vacuum circuit breaker features a three-phase post-type design. The vacuum interrupter is housed in a hollow porcelain post insulator, which is filled with sulfur hexafluoride (SF6) or nitrogen at a pressure of 0.5 MBar above atmospheric pressure to prevent the effects of condensation. The spring operating mechanism is located in a compartment that is protected from external environmental influences. The circuit breaker is mounted on a frame fabricated from welded angle steel. The simple and reliable spring operating mechanism requires low operating force and ensures an extended service life.
Main advantages
- Maintenance-free pole assembly
- Suitable for auto-reclosing
- Electroplated aluminum pole top cover
- Inspection window facing the mechanical operation indicator, located on the support box beneath the pole assembly
Main characteristics
- Rated voltage: …40.5 kV
- Rated current: …2500 A
- Rated short-circuit breaking current: … 31.5 kA
- Class C2-E2-M2-S2 circuit breaker, suitable for overhead line and cable systems and capable of withstanding higher transient recovery voltages
- Based on ABB's proven vacuum interruption technology, offering extended electrical life and an extremely low rate of restrikes
- Simple and reliable spring operating mechanism reduces operating energy and ensures extended mechanical life
- Vacuum interruption minimizes environmental impact